07/2015
Temperature Difference Controller TDC 3
Page 5 of 47
B.1 Specifications
Electrical specifications:
Mains voltage
230 VAC +/- 10%
Mains frequency
50...60 Hz
Power consumption
2 VA
Switched power
Electronic relay R1
min.20 W...max.120 W for AC3
Mechanical relay R2
460 VA for AC1 / 185 W for AC3
Internal fuse
2 A slow-blow 250 V
Protection category
IP40
Protection class
II
Sensor inputs
3 x Pt1000
Measuring range
-40° C up to 300° C
Permissible ambient conditions:
Ambient temperature
for controller operation
0° C...40° C
for transport/storage
0° C...60° C
Air humidity
for controller operation
max. 85 % rel. humidity at 25° C
for transport/storage
no moisture condensation permitted
Other specifications and dimensions
Housing design
2-part, ABS plastic
Installation methods
Wall installation, optionally panel installation
Overall dimensions
163 mm x 110 mm x 52 mm
Aperture installation
Dimensions
157 mm x 106 mm x 31 mm
Display
Fully graphical display, 128 x 64 dots
Light diode
Multi-color
Operation
4 entry keys
Temperature sensors:
(may not be included in the scope of supply)
Collector or boiler sensor
Pt1000, e.g. immersion sensor TT/S2 up to 180° C
Storage tank sensor
Pt1000, e.g. immersion sensor TT/P4 up to 95° C
Pipe-mounted sensor
Pt1000, e.g. pipe-mounted sensor TR/P4 up to 95° C
Sensor leads
2 x 0.75 mm² extendable up to 30 m max.
Temperature resistance table for Pt1000 sensors
°C
0
10
20
30
40
50
60
70
80
90
100
Ω
1000
1039
1077
1116
1155
1194
1232
1270
1308
1347
1385