6.2 CALIBRATING VALVE POSITION
The valve must be calibrated to ensure the position of the valve is accurate.
Press & hold both the open & close buttons for approximately 15 seconds to access the setup menu with the OEM
Configuration option visible.
Navigate to the Valve Calibration screen - Menu location: Setup Menu → OEM Configuration → Valve Setup → Valve
Calibration.
The screen will display the following warning: “The valve will fully open and close during calibration.” After you have
verified that the valve is properly installed to the motor, and there is no danger of damage due to water in the line,
press ■ START to begin the calibration process.
The valve will fully open and close twice to calibrate the valve position sensor. After calibration is complete, press the
■ OK button to return to the Valve Setup screen.
7 OPERATIONAL FEATURES
The Style 9333/9335 Navigator Pro Controller has been designed to be intuitive and easy to use. Once configured,
the operation is simple. Basic operation of the controller is described below.
7.1 Opening and closing the valve
To open the valve using the Navigator Pro, press the GREEN button. To close the valve, press the RED button. As
soon as either button is released, the valve will stop moving. To continue opening or closing the valve, continue to
hold the appropriate button.
Wiring Harnesses & Components
Description
Part Number
9333 Valve Controller
93330001
9335 Valve Controller
93350001
Power Harness
721359
Motor Driver
124647
Motor Extension Harness
721769
Main Harness – 10’
721618
Main Harness – 15’
721619
Main Harness – 20’
721620
Pressure Transducer Adapter Harness
721770
Flow Sensor Adapter Harness
721771