STAR 4W (4 WIRES) 3PH-4W LV

Voltage connection: 

Use cables with max cross-section of 2,5 mm

2

 if stranded 4 mm

2

 if rigid and connect them to the clamps marked VOLTAGE INPUT on the instrument according 

to the  applicable diagrams that follow. 

Current connection

: It is necessary to use external CTs with a primary rating adequate to the load  to be measured and with a 5A or 1A secondary rating. Connect the CT output(s) to 

the terminals marked I1, I2, I3 (CURRENT INPUT) of the instrument according to the applicable diagrams that follow. Use cables with cross-section adequate to the VA rating of the CT 
and to the distance to be covered. The max cross-section for the terminals is  2,5 mm

2

 if stranded and 4 mm

2

 if rigid.

Note:

 The CT secondary must always be in short circuit when not connected to the instrument in order to avoid damages and risks for the operator.  

Scrupulously respect the matching of phase between the voltage signals and current signals  (RTD) and the direction of insertion of CT (P1-P2 and S1-S2). Failure to comply with this 
correspondence and connection diagrams gives rise to measurement errors. (*) The grounding of S2 must be close to the CT and not near the instrument.

VOLTAGE AND CURRENT CONNECTION

STAR 4W (4 WIRES) 3PH-4W MV

SINGLE PHASE (2 WIRES) 1PH-2W

TRIANGLE 3W (3 

WIRES) 3PH-3W

TRIANGLE 2CT (3 

WIRES) 3PH-3W

TRIANGLE 2CT(3 

WIRES) 3PH-3W MV

BI-PHASE (2 

WIRES) 2PH-2W

 Made   

 

in   

 

Italy

Pensato, progettato e prodotto in Italia

Engineered and manufactured in Italy

12

20

19

10 11

AUX IN/OUT

S1 S2 S1 S2 S1 S2

I1

I2

I3

VOLTAGE INPUTS

POWER
SUPPLY

RS-485

CURRENT INPUTS

18

17

V1 V2 V3 N

A B

T

21

EXPBUS

ETHERNET

L1

N

S1

S2

P1

P2

12

20

19

10 11

AUX IN/OUT

S1 S2 S1 S2 S1 S2

I1

I2

I3

VOLTAGE INPUTS

POWER
SUPPLY

RS-485

CURRENT INPUTS

18

17

V1 V2 V3 N

A B

T

21

EXPBUS

ETHERNET

L1

L2

S1

S2

P1

P2

12

20

19

10 11

AUX IN/OUT

S1 S2 S1 S2 S1 S2

I1

I2

I3

VOLTAGE INPUTS

POWER
SUPPLY

RS-485

CURRENT INPUTS

18

17

V1 V2 V3 N

A B

T

21

EXPBUS

ETHERNET

L1

L2

L3

S1

S2

P1

P2

S1

S2

P1

P2

12

20

19

10 11

AUX IN/OUT

S1 S2 S1 S2 S1 S2

I1

I2

I3

VOLTAGE INPUTS

POWER
SUPPLY

RS-485

CURRENT INPUTS

18

17

V1 V2 V3 N

A B

T

21

EXPBUS

ETHERNET

L1

L2

L3

S1

S2

P1

P2

S1

S2

P1

P2

S1

S2

P1

P2

12

20

19

10 11

AUX IN/OUT

S1 S2 S1 S2 S1 S2

I1

I2

I3

VOLTAGE INPUTS

POWER
SUPPLY

RS-485

CURRENT INPUTS

18

17

V1 V2 V3 N

A B

T

21

EXPBUS

ETHERNET

L1

L2

L3

N

S1

S2

P1

P2

S1

S2

P1

P2

S1

S2

P1

P2

12

20

19

10 11

AUX IN/OUT

S1 S2 S1 S2 S1 S2

I1

I2

I3

VOLTAGE INPUTS

POWER
SUPPLY

RS-485

CURRENT INPUTS

18

17

V1 V2 V3 N

A B

T

21

EXPBUS

ETHERNET

L1

L2

L3

S1

S2

P1

P2

S1

S2

P1

P2

S1

S2

P1

P2

12

20

19

10 11

AUX IN/OUT

S1 S2 S1 S2 S1 S2

I1

I2

I3

VOLTAGE INPUTS

POWER
SUPPLY

RS-485

CURRENT INPUTS

18

17

V1 V2 V3 N

A B

T

21

EXPBUS

ETHERNET

L1

L2

L3

S1

S2

P1

P2

S1

S2

P1

P2

12

20

19

10 11

AUX IN/OUT

S1 S2 S1 S2 S1 S2

I1

I2

I3

VOLTAGE INPUTS

POWER
SUPPLY

RS-485

CURRENT INPUTS

18

17

V1 V2 V3 N

A B

T

21

EXPBUS

ETHERNET

L

N

FUSE
(500mA T)

85 ÷ 265 V ±10%

The  instrument  is  fi tted  with  a  separate  power  supply.  The  power  supply  terminals  are 
numbered (17 e 18). Use cables with max cross-section of 2,5 mm

2

 if stranded, 4  mm

2

 if 

rigid.

POWER SUPPLY