6 Installation
Must be observed:
– operating conditions from the
when choosing an installation site;
– safety requirements from the
during installation.
6.1 Mounting
– According
.
– Wire external connections in accordance with
using plug-in terminal blocks
(included).
Removal
– Take off the terminal blocks without
disconnecting the wires.
– Insert a screwdriver into the eyelet of the slide
interlock, push it, then remove the device from
the rail (
).
A
B
Fig. 6.1
6.2 Wiring
WARNING
The device must be powered off before connecting to other equipment or PC. Switch
on the power supply only after the wiring of the device has been completed.
NOTICE
Ensure that the input signal is connected to the correct input terminals and that the
input configuration corresponds to the signal. Non-observance can cause the device
damage.
NOTE
To ensure compliance with the EMC requirements:
–
Signal cables should be routed separately or screened from supply cables.
–
Shielded cable should be used for signal lines.
– The electrical connections are shown in
and the terminal assignments in
.
– Connect the power supply to the terminals 24V / 0V.
– The maximum conductor cross-section for power supply is 1.5 mm².
– The USB interface enables hot plugging. The USB cable length should not exceed 3 m.