Appendix A. Modbus application
35
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
No
Parameter
Register
Valid
value
Description
Data type
Default
(Comment)
11
UINT32
12
FLOAT32
7
Decimal point
0x0116
-5...5 (INT, UINT)
UINT16
0
0...5 (FLOAT)
8
Crash logging
0x0117
0
OFF
UINT16
0
1
ON
9
Threshold
0x0118,
0x0119
0…999999995904
(use format of
Data type
)
FLOAT32
0 (extra
logging
disabled)
10
Modbus
function
0x011A
0
3
UINT16
0 (Modbus)
1
4
11
Register
address
0x011B
0..0xFFFF
UINT16
0 (Modbus)
12
Group number
0x011C
0…32
group number
UINT16
0 (no group)
(Modbus)
13
Address
length
0x011D
0
8 bits
UINT16
0 (AKYTEC)
1
11 bits
14
HASH code
0x011E
0…0xFFFF
UINT16
0 (AKYTEC)
15
Index
0x011F
0…
0xFFFF
-1…32767
UINT16
0xFFFF (-1)
(AKYTEC)
NOTE
* Only one channel can be requested with read / write command.
Table A.8 Analog inputs tab*
No
Parameter
Register
Valid
value
Description
Data type
Default
(Com-
ment)
6 * 4 = 24 registers (R / W)
1
Range
0x1100...0x1105
0
4-20 mA
UINT16
0
1
0-20 mA
2
0-5 mA
2
Filter, ms
0x1106...0x110B
100…65535
UINT16
100
3
Min. physical
value
0x110C...0x1111
-10
9
…10
9
FLOAT32
0
4
Max. physical
value
0x1112...0x1117
-10
9
…10
9
FLOAT32
100
NOTE
* All channels are requested with one read / write command.