Appendix B Configuration parameters
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
34
No
Name
Display
Parameter
Valid value
Meaning
Factory
Advanced settings / LBA (Adv)
1
vSP
VSP
Setpoint Ramp
0…9999
affected by
dP
0.0
2
CntL
CntL
Control type
Pid
PID
Pid
onoF
on-of
3
HYSt
HYSt
Control hysteresis
(4)
0…9999
affected by
dP
1.0
4
onSt
OnSt
On-off stop state
(4)
ON
OFF
OFF
5
onEr
OnEr
On-off safe state
(4)
ON
OFF
OFF
6
rAmP
RAMP
“Quickly to Setpoint”
mode
ON
OFF
OFF
7
P
P
P component
(proportional band)
(5)
1…9999
affected by
dP
30.0
8
i
I
I component
(integral time)
(5)
0…3999 s
affected by
dP
100
9
d
D
D component
(derivative time)
(5)
0…3999 s
affected by
dP
20
10
db
db
Deadband
(5)
0…200
affected by
dP
0
11
oL-L
oL- L
Output lower limit
(5)
0…
oL-H
%
0
12
oL-H
oL- H
Output upper limit
(5)
oL-L
…100 %
100
13
orL
OrL
Output signal ramp
(5)
0.2…100 %/s
100
14
mvEr
MVEr
PID safe state
(5)
0…100 %
0
15
mdSt
MdSt
PID stop state
(5)
mvSt
mvSt
value
mvSt
o
last output value
16
mvSt
MVSt
PID stop level
(5)
0…100 %
0
17
LbA
LbA
LBA time
(5)
0…9999 s
disabled when
LbA
= 0
0
18
LbAb
LbAb
LBA range
(5)
0…9999 s
not displayed
when
LbA
= 0
10.0
RS485 network (Comm)
1
Prot
Prot
Protocol
OWEN
akYtec
OWEN
M.RTU
Modbus RTU
M.ASC
Modbus ASCII
2
bPS
BPS
Baud rate
2.4…115.2
kbit/s
115.2
3
A.LEn
A.LEN
Address bits
8
8
11
4
Addr
Addr
Address
(6)
0
5
rSdL
RSdL
Response delay
1…45 ms
20
Manual control (LmAn)
1
o-Ed
O- ED
Manual output signal
0…100 %
Manually set out-
put signal
0.0
2
o.
O.
Manual control
0…100 %
Currnet output
signal
Read
only
(1)
Displayed for temperature sensor only