Installation and Operating Manual (translation)
28
AL-KO EASYAIR
®
5.5
Mechanical connection
WARNING
Risk of crushing
When installing the duct connections as well as the intake and exhaust hoods, the multi-leaf
damper must be closed. When closing the multi-leaf damper, there is a risk of crushing inju-
ries to the hands.
Do not reach into the damper when closing the multi-leaf damper.
Wear the personal protective equipment.
5.5.1 Duct connection
The duct system of the ventilation directs the outdoor air to the air handling unit and as supply air into the building. The
exhaust air is passed through the unit and to the outside as exhaust air for heat recovery.
Duct connectors (option)
For all EASYAIR
®
air handling units, you will receive attached, sound-decoupled connectors that use the entire free unit
cross-section.
The connection of the ventilation ducts to the unit must be carried out professionally.
The duct connection must be mounted distortion-free and free of load on the EASYAIR
®
air handling unit!
Establish pre-assembled equipotential bonding on the duct.
Requirements for the duct system
In favour of efficiency, energy consumption and air performance of the unit, the pipe system must be designed for slow
flow speeds and low pressure drop.
All connections between the ventilation ducts and air handling unit must be designed and secured to fit exactly.
Inspection openings must be provided.
Condensation protection/thermal insulation
Outdoor air and exhaust air ducts must always be well insulated to protect against condensation.
Careful insulation of all ventilation ducts leading directly to the unit and in cold rooms/zones is particularly impor-
tant.
5.5.2 Intake and exhaust hood (option)
For a weatherproof version, an optional intake and exhaust hood can be ordered.
For units without a factory-delivered intake hood, a drain tray must be provided on site at the unit inlet and in the
duct.
To avoid short-circuit currents, these position and orientation of these hoods must be adjusted, depending on the
local conditions, using the on-site duct sections.
For weatherproof implementation, the optionally available intake/exhaust hoods are only attached to the unit for
transport. The applicable rules/standards regarding the fresh air intake and the exhaust air outlet must be complied
with in this regard.
Summary of Contents for EASYAIR RO-01
Page 1: ...COMPACT AIR HANDLING UNIT EN INSTALLATION AND OPERATING MANUAL AL KO EASYAIR EN ...
Page 71: ...Subject to changes in line with technical progress 71 3313737 Notes ...
Page 72: ...Installation and Operating Manual translation 72 AL KO EASYAIR Notes ...
Page 73: ...Subject to changes in line with technical progress 73 3313737 Notes ...
Page 74: ......
Page 75: ......