Assembly
3313737
Supply air temperature sensor
To measure the supply air temperature without interference, the supply air sensor must be installed in the duct be-
hind the air handling unit. Assembly directly at outlet of the supply air duct is ideal.
ETA
SUP
ODA
EHA
2
3
1
1
Position of outdoor air temperature sensor (ODA)
3
Position of supply air temperature sensor* (SUP)
2
Position of exhaust air temperature sensor (ETA)
* Assemble supply air temperature sensor (SUP) at least 3 m behind the unit!
5.6.4 Connection of electric air heater (option)
An electric air heater is optionally available for heating the supply air.
The additional unit must be flanged to the main unit (see chapter
“5.3 Assembly of separated housing” on page
25).
The electrical connection is to be carried out professionally on-site.
WARNING
Risk of injuries due to incorrect or faulty connection.
Only have the electrical connection carried out by an approved electrician.
Only have assembly, servicing and maintenance carried out by qualified staff.
Wear personal protective equipment.
CAUTION
Risk of burns due to contact with the hot electric air heater.
Wait until the hot electric air heater has cooled down.
Wear personal protective equipment.
The air heater is included in the regulation for the room or exhaust air temperature and is continuously regulated accord-
ing to temperature requirements. The air heater is equipped with an integrated safety temperature limiter and air flow
monitor.
For the use of an electric air heater, DIN VDE 0100-420 must be observed.
A separate mains supply is required for the electric air heater.
Connect the air heater electrically according to the circuit diagram.
NOTE
If the electric heating register is the last component before the on-site duct, a duct-side in-
spection opening must be provided directly on the register.
Summary of Contents for EASYAIR RO-01
Page 1: ...COMPACT AIR HANDLING UNIT EN INSTALLATION AND OPERATING MANUAL AL KO EASYAIR EN ...
Page 71: ...Subject to changes in line with technical progress 71 3313737 Notes ...
Page 72: ...Installation and Operating Manual translation 72 AL KO EASYAIR Notes ...
Page 73: ...Subject to changes in line with technical progress 73 3313737 Notes ...
Page 74: ......
Page 75: ......