Installation and Operating Manual (translation)
40
AL-KO EASYAIR
®
Set the time, date, average and low air performance, and program the weekly schedule.
Commissioning of the electric heating register (option):
IMPORTANT
Electric heating register (option)
Check safety chain: Test the function of the flow monitor and temperature monitor and adjust
these if necessary. This is the only way to ensure safe operation of the air handling unit!
6.4.1 Damper adjustings actuators
4
5
2
3
1
1
Direction of rotation switch
Changeover
Change direction of rotation
2
Pushbutton and LED display green
Off
No electrical power supply or malfunction
Glowing green
Operation
Green glowing
In address mode: Pulses according to the set address (1 ... 16)
When starting: Reset to factory setting (communication)
Press the
button
In normal operation: Triggering the rotational angle adaptation
In address mode: Confirmation of the set address (1 ... 16)
3
Pushbutton and LED display yellow
Off
Drive is ready for operation
Yellow flashing
Adaptation or synchronisation process active
Yellow flick
-
ering
Communication active
Press the
button
In operation (>3 s): Switching the address mode on and off
In address mode: Setting the address by multiple actuation
When starting (>5 s): Reset to factory setting (communication)
4
Gear disengagement button
Press the
button
Gear disengaged, motor stops, manual adjustment possible
Release button Gear engaged, start of synchronisation, afterwards normal opera-
tion
5
Service plug
For connecting the parameterisation and service tools
Summary of Contents for EASYAIR RO-01
Page 1: ...COMPACT AIR HANDLING UNIT EN INSTALLATION AND OPERATING MANUAL AL KO EASYAIR EN ...
Page 71: ...Subject to changes in line with technical progress 71 3313737 Notes ...
Page 72: ...Installation and Operating Manual translation 72 AL KO EASYAIR Notes ...
Page 73: ...Subject to changes in line with technical progress 73 3313737 Notes ...
Page 74: ......
Page 75: ......