Installation and Operating Manual (translation)
48
AL-KO EASYAIR
®
8.4
Maintaining and cleaning components
All installed components are either freely accessible for maintenance and cleaning or can either be removed or pulled out
from the unit after removing the inspection doors/inspection covers.
Coarse dirt in the housing can be removed using an industrial vacuum cleaner.
Remove other dirt with a damp cloth.
Only lukewarm water, possibly with a mild detergent without perfume, should be used for cleaning.
If disinfection is necessary for hygiene units, a checked must be performed at a suitable and non-critical point before
using disinfectants to ensure that the disinfectant does not cause damage to the seals, surfaces, etc.!
Only use cleaning agents and disinfectants that do not attack the materials used in the EASYAIR
®
unit!
The aim of the hygiene checks to be performed regularly is to determine and eliminate hygiene deficiencies on the air
conditioning systems at an early stage through frequent visual inspections or random microbiological self-checks.
The regular hygiene checks include the following measures:
Visual inspection of the relevant unit area for hygiene deficiencies such as e.g. microbial growth or soiling, rust for
-
mation, calcium deposits and damage.
If soiled components are detected during the hygiene checks, these must be cleaned immediately.
8.4.1 Pump warm water and pump cold water heat exchangers
WARNING
Risk of cuts
During maintenance and cleaning of the heat exchanger there is a risk of cuts!
Wear personal protective equipment (cut-proof gloves)!
CAUTION
Risk of burns as a result of contact with hot surfaces and media (plate heat exchanger,
heat exchanger and electric heating register).
Wait until the hot surfaces have cooled down.
Wear personal protective equipment.
IMPORTANT
The use of high-pressure water cleaners with conventional single-jet nozzles is not permitted
due to the risk of damage!
Summary of Contents for EASYAIR RO-01
Page 1: ...COMPACT AIR HANDLING UNIT EN INSTALLATION AND OPERATING MANUAL AL KO EASYAIR EN ...
Page 71: ...Subject to changes in line with technical progress 71 3313737 Notes ...
Page 72: ...Installation and Operating Manual translation 72 AL KO EASYAIR Notes ...
Page 73: ...Subject to changes in line with technical progress 73 3313737 Notes ...
Page 74: ......
Page 75: ......