Assembly
3313737
5.5.3 Siphon connection
Condensate drain lines must be connected to the drain system with a snake siphon. A direct connection of water
drains to the drain system is not permitted!
NOTE
The standing height of the respective siphon must be designed for the underpressure or over-
pressure of the air handling unit to prevent suction or blowing out of air from the closed drain
pipe. For a weatherproof version, the pipe trace heating is to be provided. The pipeline must
be protected against environmental influences.
Drain pipe 40 on-site
H2
H1
H3
*Dimension H3 below equipment installation level
Height
minimal
maximal
Overpressure up to 800 Pa
Vacuum up to 800 Pa
H1
0
130 mm
50 mm
mm WC + 50 mm
H2
55 mm
145 mm
1.5 * mm WC + 25 mm
mm WC / 2 + 50 mm
H3
100 mm
210 mm
H2 + 40 mm
H1 + H 2 - 10 mm
WC = water column
10 Pa = 1 mm WC
NOTE
The installation height of the siphon must be taken into account when setting up the unit.
Observe minimum dimensions H1-H3!
40
30
Floor drain
40