Subject to changes in line with technical progress.
55
Servicing and maintenance
3313737
8.4.6 Fans
WARNING
Risk of injuries due to overrun of fans.
Switch off the unit on all poles and secure it against being restarted.
Only open the inspection doors only when the fans are switched off and stationary.
Observe the delay time of the fans. Observe a waiting time of at least 3 minutes, until the
fan impellers are stationary, before opening the inspection doors.
Never brake the impellers of the fans by hand or using an object.
WARNING
Risk of cuts
There is a risk of cuts during maintenance and cleaning of the fans!
Wear personal protective equipment (cut-proof gloves)!
8.4.6.1 Maintenance
The ball bearings used are low-maintenance and designed for extended running times. They can normally be used up to
+40 °C. Maintenance is not required under normal conditions.
Check fans for dirt, damage and corrosion.
Check fan mounting and retighten all fastening screws.
Check the function of the protective devices.
8.4.6.2 Cleaning
Clean the ventilation wheel, motor and motor mounting regularly.
8.4.7 Sound absorbers
WARNING
Risk of cuts
During maintenance and cleaning of the sound attenuator splitters there is a risk of cuts!
Wear personal protective equipment (cut-proof gloves)!
8.4.7.1 Maintenance
The sound absorbers must be inspected for soiling and damage at regular intervals.
8.4.7.2 Cleaning
Sound attenuator splitters can be removed from the unit for cleaning.
Recommendation: Following extended operating intervals, clean the sound attenuator splitters using an industrial
vacuum cleaner.
Summary of Contents for EASYAIR RO-01
Page 1: ...COMPACT AIR HANDLING UNIT EN INSTALLATION AND OPERATING MANUAL AL KO EASYAIR EN ...
Page 71: ...Subject to changes in line with technical progress 71 3313737 Notes ...
Page 72: ...Installation and Operating Manual translation 72 AL KO EASYAIR Notes ...
Page 73: ...Subject to changes in line with technical progress 73 3313737 Notes ...
Page 74: ......
Page 75: ......