2.5.4. Installed Cascade System Dimensions
2.5.5. Sanitary Needs For a Long Boiler Life and Proper Operation
Whether your system will be self operating or in a cascade setup, the installations must always
include
• Oxygen seperator
• Hydraulic header (in PVC circuitry, a plate heat exchanger should be used)
• Silt trap / strainer
• Expansion vessel (per each boiler)
in order for a long life of your device and the validity of your warranty.
horizontal
from wall to pipe axis
107 mm
357 mm
122 mm
min 200 mm
min 200 mm
165 mm
36 mm
18 mm
0
59
7 m
m
165 mm
The flue collector pipe’s slope used for cascade systems will be nearly 1,5o. Every additional
collector pipe adds nearly an 18 mm’s on the total height of the installed system.