INSTALLATION
The design, installation and commissioning of the heating system must be carried
out
in accordance with the applicable standards, regulations and the warnings in this
manual.
In cases where there are no local standards, regulations or inadequate standards
and regulations,
EEC directives and European norms (EN) should be applicable.
• The control and commissioning of the entire system must be carried out by
Alarko Carrier Authorized Services.
• The boiler must be installed in a closed area, except for living areas, which
are well ventilated and where there is no risk of freezing in accordance with
the rules. Top and bottom ventilation systems must comply with local
regulations.
• Boilers must only be used with EN 676 (gaseous fuel) or EN 267 (liquid fuel)
certified burners to operate in accordance with the Directive (92/42/AT) on
Efficiency Requirements for Boilers and the Directive 2009/142/EC on
Appliances Burning Gaseous Fuels.
• This is a B23 type boiler, so the boiler must be connected to a flue with
sufficient draught in accordance with the regulations, and there should be no
flue gas leakage into the boiler room.
• All equipment and control system of the heating system should be able to
provide the specified heating loads according to the external climatic
conditions and the desired internal temperature. It should be able to protect
the heating system against freezing and humidity when normal operating
conditions (comfort temperature level) are not required.
• The equipment for the control and safety systems of the heating system must
comply with the applicable TS standards, and, where insufficient, the
instructions in EN 12828 and this manual must be observed.
• The heating system must also have at least one circulation pump complying
with the system requirements and this pump must be kept in operation as
long as the burner is operating.
• An effective installation circuit must be installed to protect the boiler from flue
gas condensation. The condensation return water temperature should be
kept above the condensation value by a system such as condensation by
pass pump, 3-way valve system.
• The first filling water and then the feeding water should have the properties
specified in this manual. The use of water with proper properties is necessary
for the longevity of the system and its economic operation. Extremely soft
water causes corrosion, extremely hard water causes limestone, so water
with proper values should be used.
18