31
COMMISSIONING
Installation control and first operation must be carried out by Alarko Carrier
Authorized Services and necessary documents must be recorded. Otherwise,
the manufacturer and/or the dealer shall not accept any liability for any matter
and the product is deemed to be out of warranty.
Before starting the first operation, please check the following matters;
• The availability of the installation, commissioning, operating,
maintenance and repair of the heating system equipment in the boiler
room.
• Compliance of the system requirements and equipment with the values
indicated on the boiler label. Fuel type and pressure, boiler - burner
capacity, electrical energy values, filling water properties, expansion
system existence and adequacy, selection of operating pressure and
temperature according to the system requirements... etc.
• Existence and adequacy of boiler room ventilation. The ventilation is
not blocked by any obstruction.
• The flue gas ducts and the flue are adequate and installed correctly.
• Ensure that all system controls and safety equipment are available,
have the correct properties, and are installed correctly and that they are
all operating in the desired range of values.
• Fuel type and burner capacity are selected correctly according to boiler
and heating system requirements.
• If gaseous fuel is used, the turbulators are present complete in the
boiler and have been placed correctly.
• If liquid fuel is used, the turbulators have been removed.
• There is no forgotten foreign material in the boiler combustion chamber.
• Boiler front cover, back cover, burner adapter plate, window box seals
are intact and installed correctly.
• The gap between the burner barrel and the cover refractory is
insulated, the suitability of the length of the burner connection bolts.
• Check that if the burner is heavy, a carrier support is placed under it,
and that flue ducts load is not carried by the boiler smoke outlet.
• In the installation criteria, the warnings specified in this manual and the
applicable standards and regulations are taken into account.