35
Start Up
Standard control panel;
Turn on the main burner switch (if equipped and in the closed position).
Turn on the control panel switch.
Adjust the boiler thermostats to the desired level. (If there is a 2nd stage
thermostat, set it to 7 °C below the degree of the 1st stage thermostat).
Switch on the circulation pump.
The burner will be activated after finishing the standard automatic control functions.
If the burner does not switch on and the fault lamp on the burner is illuminated,
reset it by pressing. Call your authorized dealer if it is not activated when you try it
for 3 times.
(Visually check that there is no leakage of combustion gases from the boiler front
and rear cover area and from the flue connections after each commissioning).
Stop
Standard control panel;
a) If there is a 2nd stage thermostat in your control panel, first set the 2nd
stage thermostat to minimum (If the thermostat is operating normally, the
burner will immediately switch to 1st stage operation. This function is a
practical way to control the 2nd stage thermostat).
If the control panel is single stage, start from the section ”b“.
b) Set the boiler thermostat to minimum (If the boiler thermostat is working
normally, the burner will stop immediately. This function is a practical way to control
the boiler thermostat).
Turn off the burner control main switch.
Turn off the main fuel valve.
For long-term shutdowns: you can stop the circulation pump, but keep in mind
that the water in motion is more difficult to freeze. If you shut the system off for
a long period in winter, make sure that the heating system and other parts are
protected against frost.
If there is another type of control panel, refer to the relevant manual.