Beacon Power Supply Installation Instructions
2.8.2012
52-296 Rev B05
Page 17 of 27
AlarmSaf
65A Industrial Way, Wilmington, MA 01887 978 658 6717 www.alarmsaf.com
Section 5
Operating the BNx000
5.1 Output Voltage Selection
Before powering a system containing a BNx000, the output voltage switch (S1 - Voltage Select)
must be set for the proper output voltage or damage to the system could occur. Do not change
the switch setting while the unit is powered or damage to the system may occur. Set the
switch UP for 24V, DOWN for 12V (the PC board is labeled with the voltage settings).
12
24
VOLTAGE
SELECT
4000
6000
8000
10000
Figure 5.1.1
5.2 Jumper Settings
For proper operation, the jumpers on the BNx000 should be set appropriately. All jumpers
should be verified or set before powering the unit.
Jumper
Description
Settings
Default
JP1 (BPD)
Battery Presence
Up (D) - Disable
Down - Enable
Down - Enable
JP2 (SPV)
N/A
Up
Up
JP3 (D/E)
FAI Filtering
Left (D) - Disable
Right (E) - Enable
Left (D) - Disable
J5 (VAC SELECT)
Input Voltage Configuration
Up (120) - 120VAC Input
Down (240) or Removed- 240 Input
Up (120) - 120VAC
Note: Jumper positions are referenced with the output wiring terminal blocks (TB1&2) on the bottom
5.2.1 JP1 (BPD) - Battery Presence
Allows disabling of the battery presence detection for applications where no backup battery set
is used.
5.2.2 JP2 (SPV)
This jumper serves no user function and, if present, should be left in the up position.