I.

Model Numbers

8Ah Max

28.2VAC

2.50A

36Ah

4.0A

24VDC

PS5-24040-B03-UL/CSA/ULC

 013XX

20Ah Max

17.5VAC

1.25A

36Ah

4.0A

12VDC

PS5-12040-B03-UL/CSA/ULC

 013XX

8Ah Max

28.2VAC

2.50A

38Ah

4.0A

24VDC

PS5-BFS-24-UL/CSA/ULC

 01310

20Ah Max

17.5VAC

1.25A

38Ah

4.0A

12VDC

PS5-BFS-12-UL/CSA/ULC

 01309

Battery

Storage in

Cabinet

XFMR

Voltage

Max. AC

Input

Current

Max.

Battery

Capacity

System
Current

System
Voltage

Model Number

AS

Order

No.

       UL1481 - Power Supply/Battery Charger, Guide UTRZ

Power Supply/Battery Charger for use with Listed devices shown in Addendum "A".

       UL294 - Access Control Systems Unit Accessory, Guide ALVY

Power Supply/Battery Charger for Access Control Applications

       ULC-S527 - Fire Alarm Power Supply/Battery Charger
       CSA C22.2 No. 107.1 - Commercial and Industrial Power Supply
* UL Listed Products comply with NFPA 72 - National Fire Alarm Code, and are CSFM Listed 
  #7315-1214:100 and NY MEA Accepted #MEA 3-92-E

II.

Installation Instructions

1. Mount cabinet per mechanical dimensions and knockout locations given in Section IV.
2. Connect 120VAC, 60Hz., single phase to the black and white leads of the transformer in accordance

with Article 725 or 760 of the National Electrical Code, or Article 16 or 32 of the Canadian Electrical
Code.

3. Low Volt AC Input - Connect to secondary winding of the transformer.

v

 Fused at 10 Amps (Fuse Type AGC-10)

4. Verify output voltage at "DC Output" and "Battery" terminals.

12V system measures approximately 13.8VDC.
24V system measures approximately 27.6VDC.

5. Connect battery set to "Battery" terminals.

CAUTION: Observe polarity; incorrect polarity will destroy battery fuse.
Fused at 10 Amps (Fuse Type AGC-10).
Recommended battery type - PowerSonic (PSSeries) or YUASA (NPSeries) sealed lead acid/gel cell.

6. Connect "DC Output" to input of user system.

CAUTION: Observe polarity; incorrect polarity may damage user system.
Refer to Section I for Maximum Allowable System Current.

7. Visual Indicators:

AC Presence LED1:

Green LED

Fault Condition LED3:

Yellow LED (PS5-BFS)

System OK LED3:

Green LED (PS5-B03)

8. Connect "Fault Output" to system fault annunciation.

PS5-BFS Models: Current limited voltage output

12V system; short circuit fault current is 25mA maximum.
24V system; short circuit fault current is 50mA maximum.

For fault reporting in fire applications, use Relay Module RBKS-124P or RBKS-124N: See Section III.
PS5-B03 Models: Form "C" relay contacts; rated 1A @ 24VDC

9. Fault Conditions:

Low AC / No AC / Blown AC Fuse / Low Battery / Blown Battery Fuse

CAUTION: Fault condition reporting may be delayed dependent on power supply loading.
The battery set is NOT supervised for presence.

10. This unit is intended to be placed in the same room as the control equipment.
11. UL and ULC Battery Standby Information for proper operation of this unit:

a. For 60 hr. standby with 18Ah battery set: Max standby draw: .15A, Max 5 minute alarm current: 3A.

b. For 24 hr. standby with 18Ah battery set: Max standby draw: .4A,
Max 5 minute alarm current: 3A.
c. For 60 hr. standby with 36Ah battery set: Max standby draw: .5A,
Max 5 minute alarm current: 2A.
d. For 24 hr. standby with 36Ah battery set - Max standby draw: 1A,
Max 5 minute alarm current: 2A.
e. For 4 hr. standby with 20 Ah battery set - Max standby draw: 3A,
Max  5 minute alarm current: 4A.

12. Power Supply System Draw (No AC, No load) is 25mA.

III.

Typical Hook-up Diagrams

{

To Convert the Voltage Fault Output to a Form C relay contact output
The relay will activate on a fault condition.

{

To Convert the Voltage Fault Output to a Form C relay contact output
The relay will deactivate on a fault condition (Fail-Safe Supervision)

            Power Supply/Battery Chargers

                      Installation Instructions

AlarmSaf

 

w

 

65A Industrial Way 

w

 Wilmington, MA USA 01887-3499 

w

 (978) 658-6717 

w

 FAX: (978) 658-8638  Web Site:  www.alarmsaf.com

52-130Z

090897

 

{

Power Supply Output
Terminal Designations

Caution

For continuous protection against

fire hazard, replace only with the

same type and rating of fuse

Caution: Voltage Fault Output

Not for Fire Protective

Signaling Use.

Use for general purpose only.

Low Voltage
AC Connect

Battery
Connect

AC Fuse

AGC-10

AC

LED

AGC-10

Battery
Fuse

PS5-UL Board

DC

Output

+

Fault
Output

DC

Output

+

+

Fault
Output

Fault
LED

PS-5 UL Board With Relay

+

Low Voltage
AC Connect

Battery
Connect

AC
LED

NC

C

NO

Fault
LED

AC Fuse

AGC-10

AGC-10

Battery
Fuse

Reviews: