I.
Model Numbers
8Ah Max
28.2VAC
2.50A
36Ah
4.0A
24VDC
PS5-24040-B03-UL/CSA/ULC
013XX
20Ah Max
17.5VAC
1.25A
36Ah
4.0A
12VDC
PS5-12040-B03-UL/CSA/ULC
013XX
8Ah Max
28.2VAC
2.50A
38Ah
4.0A
24VDC
PS5-BFS-24-UL/CSA/ULC
01310
20Ah Max
17.5VAC
1.25A
38Ah
4.0A
12VDC
PS5-BFS-12-UL/CSA/ULC
01309
Battery
Storage in
Cabinet
XFMR
Voltage
Max. AC
Input
Current
Max.
Battery
Capacity
System
Current
System
Voltage
Model Number
AS
Order
No.
UL1481 - Power Supply/Battery Charger, Guide UTRZ
Power Supply/Battery Charger for use with Listed devices shown in Addendum "A".
UL294 - Access Control Systems Unit Accessory, Guide ALVY
Power Supply/Battery Charger for Access Control Applications
ULC-S527 - Fire Alarm Power Supply/Battery Charger
CSA C22.2 No. 107.1 - Commercial and Industrial Power Supply
* UL Listed Products comply with NFPA 72 - National Fire Alarm Code, and are CSFM Listed
#7315-1214:100 and NY MEA Accepted #MEA 3-92-E
II.
Installation Instructions
1. Mount cabinet per mechanical dimensions and knockout locations given in Section IV.
2. Connect 120VAC, 60Hz., single phase to the black and white leads of the transformer in accordance
with Article 725 or 760 of the National Electrical Code, or Article 16 or 32 of the Canadian Electrical
Code.
3. Low Volt AC Input - Connect to secondary winding of the transformer.
v
Fused at 10 Amps (Fuse Type AGC-10)
4. Verify output voltage at "DC Output" and "Battery" terminals.
12V system measures approximately 13.8VDC.
24V system measures approximately 27.6VDC.
5. Connect battery set to "Battery" terminals.
CAUTION: Observe polarity; incorrect polarity will destroy battery fuse.
Fused at 10 Amps (Fuse Type AGC-10).
Recommended battery type - PowerSonic (PSSeries) or YUASA (NPSeries) sealed lead acid/gel cell.
6. Connect "DC Output" to input of user system.
CAUTION: Observe polarity; incorrect polarity may damage user system.
Refer to Section I for Maximum Allowable System Current.
7. Visual Indicators:
AC Presence LED1:
Green LED
Fault Condition LED3:
Yellow LED (PS5-BFS)
System OK LED3:
Green LED (PS5-B03)
8. Connect "Fault Output" to system fault annunciation.
PS5-BFS Models: Current limited voltage output
12V system; short circuit fault current is 25mA maximum.
24V system; short circuit fault current is 50mA maximum.
For fault reporting in fire applications, use Relay Module RBKS-124P or RBKS-124N: See Section III.
PS5-B03 Models: Form "C" relay contacts; rated 1A @ 24VDC
9. Fault Conditions:
Low AC / No AC / Blown AC Fuse / Low Battery / Blown Battery Fuse
CAUTION: Fault condition reporting may be delayed dependent on power supply loading.
The battery set is NOT supervised for presence.
10. This unit is intended to be placed in the same room as the control equipment.
11. UL and ULC Battery Standby Information for proper operation of this unit:
a. For 60 hr. standby with 18Ah battery set: Max standby draw: .15A, Max 5 minute alarm current: 3A.
b. For 24 hr. standby with 18Ah battery set: Max standby draw: .4A,
Max 5 minute alarm current: 3A.
c. For 60 hr. standby with 36Ah battery set: Max standby draw: .5A,
Max 5 minute alarm current: 2A.
d. For 24 hr. standby with 36Ah battery set - Max standby draw: 1A,
Max 5 minute alarm current: 2A.
e. For 4 hr. standby with 20 Ah battery set - Max standby draw: 3A,
Max 5 minute alarm current: 4A.
12. Power Supply System Draw (No AC, No load) is 25mA.
III.
Typical Hook-up Diagrams
{
To Convert the Voltage Fault Output to a Form C relay contact output
The relay will activate on a fault condition.
{
To Convert the Voltage Fault Output to a Form C relay contact output
The relay will deactivate on a fault condition (Fail-Safe Supervision)
Power Supply/Battery Chargers
Installation Instructions
AlarmSaf
w
65A Industrial Way
w
Wilmington, MA USA 01887-3499
w
(978) 658-6717
w
FAX: (978) 658-8638 Web Site: www.alarmsaf.com
52-130Z
090897
{
Power Supply Output
Terminal Designations
Caution
For continuous protection against
fire hazard, replace only with the
same type and rating of fuse
Caution: Voltage Fault Output
Not for Fire Protective
Signaling Use.
Use for general purpose only.
Low Voltage
AC Connect
Battery
Connect
AC Fuse
AGC-10
AC
LED
AGC-10
Battery
Fuse
PS5-UL Board
DC
Output
+
Fault
Output
DC
Output
+
+
Fault
Output
Fault
LED
PS-5 UL Board With Relay
+
Low Voltage
AC Connect
Battery
Connect
AC
LED
NC
C
NO
Fault
LED
AC Fuse
AGC-10
AGC-10
Battery
Fuse