24
The reading error message appears when the test current exceeds 80 amps. This
error may be the result of a hardware failure in the Cellcorder or an out-of-
calibration condition.
_*_READING ERROR_*_
EXCESSIVE LOAD
CHECK CONNECTION
[ANY KEY]...
The low current message appears when the test current is below 20 Amps. This
may be the result of a poor test lead connection, faulty cell, hardware failure in
the Cellcorder, or an out-of-calibration condition. Press test for at least one
second to retry the test.
LOW CURRENT - CELL
OR CONNECT PROBLEM
SELECT TEST BUTTON
>1 SECOND TO RETRY
The discharge warning message appears when the battery is fully discharged.
When a low battery is detected, the unit displays this message once a minute for
five minutes and then shuts down. (Refer to
Battery Charging
.)
_ _ _*WARNING*_ _ _
Cellcorder
BATTERY LOW
- RECHARGE -
The cool down fan message appears if an attempt is made to turn off the
Cellcorder within five minutes of testing an 8V or 12V module.
COOL DOWN FAN ON
ALLOW 5 MINUTE WAIT
KEEP CASE OPEN
3.5.1 Resetting the Cellcorder
If the Cellcorder locks up (will not respond to any keys), simultaneously
press the ON and F1 buttons to manually reset the unit.
WARNING
: If a manual reset is needed, disconnect any leads connected to
the battery before initiating a reset.