Cable data - GE
The following figure displays the cable design for the Gigabit Ethernet (GE) LA cable.
As GE interfaces are bidirectional, the MDI wiring conforms to the IEEE 802.3-2002
standard. Based on this standard, the MDI-X (cross-over) functions for bidirectional GE
interfaces are not compatible with the MDI-X functions for E/FE interfaces.
The following figure displays the MDI connector for MDI-X functions and is denoted
with the symbol 'X'.
Table 4-15
Pin assignment (LAN cable - GE)
Point on connector
Signal name
MDI connector signal
name
Description
1
BI_DA +
BI_DB +
Bidirectional data,
poistive
2
BI_DA -
BI_DB -
Bidirectional data,
negative
3
BI_DB +
BI_DA +
Bidirectional data,
positive
4
BI_DC +
BI_DD +
Bidirectional data,
positive
5
BI_DC -
BI_DD -
Bidirectional data,
negative
6
BI_DB -
BI_DA -
Bidirectional data,
negative
7
BI_DD +
BI_DC +
Bidirectional data,
positive
8
BI_DD -
BI_DC -
Bidirectional data,
negative
Cable data
A standard LA cable (CAT5) can be used (100 Ω symmetrical).
Cable connection
Please connect the LA cables as shown in the figure below:
Figure 4-30 Cable design (LAN cable - GE)
System cabling
Option card cable installation
LAN interfaces (X8PL, and X5IP cards)
...................................................................................................................................................................................................................................
...................................................................................................................................................................................................................................