Local equipment and cross-connect tests
Installation tests
............................................................................................................................................................................................................................................................
365-372-304R7.1
Issue 1, November 2007
4 - 1 1
........................................................................................................................................................................................................................
7
Select the FACILITY direction.
Result:
The results should indicate that the test ran for a duration of 60 seconds
followed by 0 es (errored seconds).
........................................................................................................................................................................................................................
8
Complete the above test on all Function Unit slots terminating at DSX equipment. Once
you have completed the test make sure that all loopbacks have been removed at the
Customer Network Control Center before moving on to any other testing.
........................................................................................................................................................................................................................
9
Check off the appropriate box in
Appendix E, “Installation checklist”
.
........................................................................................................................................................
E
N D
O
F
S
T E P S
DS1 non-terminating equipment transmission testing (optical main OLIU)
Perform the following steps for all 1665 DMX shelf Function Unit slots that are cabled to
a DSX-1 and not to any terminating equipment.
A Function Unit slot cabled to the DSX-1 must contain a 28DS1 (LNW6 or LNW7)
circuit pack or a 56DS1/E1 (LNW8) circuit pack in order to perform these tests. If the
1665 DMX shelf is not fully populated, it may be necessary to move the circuit pack(s)
from slot to slot in order to test all DS1 cabling.
This procedure requires the use of a DS1 test set.
Procedure
This command creates a cross-connect to map the first DS1 of a DS1 circuit pack in a
Function Unit to the first VT1.5 within the first VT Group of STS1 of the Main OLIUs.
........................................................................................................................................................................................................................
1
Log on to the 1665 DMX shelf using the CIT software as described in the
........................................................................................................................................................................................................................
2
Select Configuration -> Cross Connections...
........................................................................................................................................................................................................................
3
Use the Cross-Connection Wizard to enter a new cross-connection at the VT1.5 rate,
UPSR Ring Add/Drop, starting with m-1-1-1-1 and fn-1-1-1 (fn will be a,b,c or d
Summary of Contents for Data Multiplexer Explore 1665
Page 8: ... Contents v i i i 365 372 304R7 1 Issue 1 November 2007 ...
Page 12: ... List of figures x i i 365 372 304R7 1 Issue 1 November 2007 ...
Page 16: ... List of tables x v i 365 372 304R7 1 Issue 1 November 2007 ...
Page 24: ... About this document x x i v 365 372 304R7 1 Issue 1 November 2007 ...
Page 272: ... Final operations Operational tests 5 2 2 365 372 304R7 1 Issue 1 November 2007 ...
Page 326: ... Cleaning pluggable optics modules Fiber cleaning B 1 4 365 372 304R7 1 Issue 1 November 2007 ...
Page 408: ...I N 4 365 372 304R7 1 Issue 1 November 2007 Index ...