Versa’larm

Operation, Maintenance and Installation Manual

Alderon Industries - Hawley, MN  |  218.483.3034  |  info@alderonind.com  |  alderonind.com

Installation of the Alarm Panel Continued

7. Connect any combination of switches (rated 9 VDC, 200mA Minimum) such as a float switch, water sensor, or sump probe 

sensor to Terminals C and 1 on the terminal block of the alarm panel. TERMINAL 2 IS NEVER USED. See below for wiring 

examples (Fig. 13). The alarm is activated by a “closed” switch. CAUTION! - When installing the “Signaling Device”, refer to 

its installation instructions for proper installation.

8. Plug the alarm panel power supply into a 120 VAC, 50/60 Hz standard 

wall outlet and the green “Power” LED should illuminate (Fig. 14).

Testing the Alarm Panel

(Fig. 13)

(Fig. 14)

Versa’larm

 Accessory (P/N: 7933)

Indoor/Outdoor LED Strobe Beacon

Red 

C

Black 

2

Use 18 gauge wire and connect Red Wire 

to Terminal C and Black Wire to Terminal 2

TERMINALS C AND 1:
Float Switch

Black = 1

White = C

WaterSpotter™ or WaterSpotter™ Probe

Black = 1

Red = C

Combination of Sensors

Blacks = 1

Reds / Whites = C

1. Test the alarm panel by pressing and holding the “Alarm Test” pushbutton 

(Fig. 15) or activating the “Signaling Device” (i.e., float switch or water 

sensor / Fig. 16). The buzzer should annunciate and the alarm LED should 

illuminate. Press the “Alarm Silence” pushbutton and the buzzer should 

silence while the alarm LED remains on. After you remove pressure from 

the “Alarm Test” pushbutton or deactivate the “Signaling Device”, the “Auto 

Reset” feature reactivates the alarm panel for the next alarm cycle. If testing 

with “Signaling Device”, make sure to test all devices for complete system 

operation. Test product weekly to ensure system integrity.

(Fig. 15)

(Fig. 16)

1-Zone Alarm - Model VA01A

5 ft. Max

Float Switch

White = C

Black = 1

X

Float Switch

White = C

Black = 1

WaterSpotter™

Red = C

Black = 1

X

Float Switch

White = C

Black = 1

WaterSpotter™

Red = C

Black = 1 WaterSpotter™ Probe

Red = C

Black = 1

X

Alarm Systems

Control Panels

Float Switches

Leak Detection Systems

Page 4 of 4

P/N: 101444

Summary of Contents for Versa'larm VA01A

Page 1: ...es battery backup during power outages The power LED green will illuminate when powered The Versa larm is a multipurpose alarm panel that can be use in a variety of applications such as septic tanks sumps holding tanks pump chambers water tanks flow pressure condensate temperature and any others where a dry contact can be connected to the alarm panel When a switch signaling device contact closes t...

Page 2: ...ntegrity Mount the alarm panel using two 6 self tapping screws not included Fig 6 Use two 8 plastic anchors not included Fig 7 if mounting the alarm panel to sheet rock Fig 5 Fig 6 Fig 7 5 ft Max Alderon Industries Hawley MN 218 483 3034 info alderonind com alderonind com 3 If auxiliary contacts are not used go to step 6 If connecting alarm to an existing system go to Figure 9 on page 3 If using a...

Page 3: ...VDC 100mA power supply for external equipment Terminals 1A and 1B Normally Open Class 2 24 VDC VAC 50 60 Hz 100 Milliamps Maximum Note The auxiliary contacts on Terminals 1A and 1B of the alarm panel are Normally Open only 1A 5 After the access cover has been removed from the alarm panel Fig 10 use a needle nose pliers not included to remove the desired break away tabs from the access cover lightl...

Page 4: ...minal 2 TERMINALS C AND 1 Float Switch Black 1 White C WaterSpotter or WaterSpotter Probe Black 1 Red C Combination of Sensors Blacks 1 Reds Whites C 1 Test the alarm panel by pressing and holding the Alarm Test pushbutton Fig 15 or activating the Signaling Device i e float switch or water sensor Fig 16 The buzzer should annunciate and the alarm LED should illuminate Press the Alarm Silence pushbu...