14
4.2. EasyVEC
®
C4 Standard 4000 :
Opérations de mise en service • Activation operations
Réglage manuel du variateur. Pour régler la consigne de pression, ajuster la consigne en % selon le tableau suivant. • Manual controller
adjustment. To adjust the pressure setpoint, adjust the setpoint % as per the next table.
ON
Consigne [%]
Setpoint [%]
Mesure de pression [Pa]
Pressure measurement [Pa]
99
1000
91
900
82
800
73
700
64
600
55
500
46
400
37
300
33
250
28
200
24
150
21
120
20
110
19
100
17
80
15
50
Désignation
Designation
Pression max. [Pa]
Max. pressure [Pa]
%
EasyVEC
®
C4 Standard 4000
400
46