29
EN
Category
Adress
(Decimal)
Adress
(Hexa)
Data
Size
(Words)
Read
Write
Comments
(0x03)
(0x10)
Identifi cation
1
$1
Machine ID code
2
x
SAP code
3
$3
Aldes serial number
4
x
12
$C
Software version
1
x
20
$14
Back-up order
Parameters
1
x
x
EasyVEC®: Storing $1213, Reset C4: $5452
21
$15
Box fan number
1
x
34
$22
Product ID
1
x
x
BMS Ventilation
Operating mode
256
$100
Control mode
1
x
x
Constant pressure self-balancing = 12
Constant pressure self-balancing = 12
Constant pressure humidity-controlled = 13
Constant pressure TFlow = 14
Constant airfl ow = 1001
Constant speed = 2
Rising curve auto = 1002
Rising curve hygro = 1003
Rising curve TFlow = 1004
Rising curve Expert = 1005
0-10 V = 1006
Operating
setting
272
$110
Exhaust Flow setpoint
1
x
x
274
$112
Extract Pressure
setpoint
1
x
x
276
$114
speed setpoint
1
x
x
284
$11C
Parameter 0-10V U1
1
x
x
285
$11D
Parameter 0-10V U2
1
x
x
286
$11E
Parameter 0-10V V1
1
x
x
287
$11F
Parameter 0-10V V2
1
x
x
288
$120
Parameter P1
1
x
x
289
$121
Parameter P2
1
x
x
291
$123
Nbr. Eyes
1
x
x
292
$124
gas option
1
x
x
Main entries
Supply
337
$151
Power supply voltage
1
x
0-10V entry
338
$152
0-10V input
1
x
C4 Mode
366
$16E
Mode C4 state
1
x
0 = shutdown, 2512 = active
Errors
384
$180
Current error code
1
x
386
$182
Previous error code
1
x
388
$184
N-2 error code
1
x
390
$186
N-3 error code
1
x
392
$188
N-4 error code
1
x
394
$18A
N-5 error code
1
x
396
$18C
N-6 error code
1
x
398
$18E
N-7 error code
1
x
400
$190
N-8 error code
1
x
Machine reboot
65534
$FFFE
Card restart
1
x
If 0xFFFE sent, the card then is reset and the
commissioning will be eliminated
Summary of Contents for 11034960
Page 1: ...www aldes com EasyVEC C4 400 4000 m3 h Notice d installation FR Installation instructions EN...
Page 10: ...10 EasyVEC C4 PRO ULTRA ULTIMATE 400 4000 2 3 1 L N 4...
Page 33: ...33...
Page 34: ...34 NOTES...
Page 35: ...35 NOTES...
Page 36: ...www aldes com 11038150 A 09 2020 RCS 956 506 828 Aldes Imprim en France Printed in France...