109
Language
With this parameter, you can select the language of all menus (except for the Factory menu, which will always be
in English).
GB
FR
ES
IT
NL
DE
HU
English language (default)
French language
Spanish language
Italian language
Dutch language
German language
Hungary language
Auto
With this parameter, you can configure a device that automatically adjusts the fan speed. See the wiring diagram
for the connection of the device.
External
signal
The fan speed will be controlled through an external 0-10V analog signal (default value); if the ex-
ternal signal takes the 0V value, the control will indicate a problem with the source of the external
signal.
AutoMin%
Corresponds to the input signal percentage value for which fans must run at the minimum speed.
AutoMax%
corresponds to the input signal percentage value for which fans must run at the maximum speed.
SP.1,2% SP.2,3% and Δ values depend on the values of parameters AutoMin% and AutoMax%
according to the following formulas:
RH sensor
The fan speed will be controlled by a relative humidity (RH) sensor with 0-10V output and will have
a linear trend between 0 and 100% RH (0V corresponds to 0% RH and 10V corresponds to 100%
RH); if the external signal of the RH sensor takes the 0V value, the control will display a problem
with the sensor.
See graphs of the segnale es parameter.
In this case,
AutoMin%
corresponds to the relative humidity value for which the air quality is held
to be excellent,
AutoMax%
corresponds to the relative humidity value for which the air quality is
held to be very bad.
CO
2
VOC
The fan speed will be controlled by a CO
2
(or CO
2
-VOC) sensor with a 0-10V output and will have a
linear trend between 0 and 2000 ppm (0V corresponds to 0% ppm and 10V corresponds to 2000
ppm); if the external signal of the CO
2
sensor takes the 0V value, the control will display a problem
with the sensor.
Where
AutoMin ppm
corresponds to the CO
2
(CO
2
-VOC) concentration for which the air quality is
held to be excellent,
AutoMax ppm
corresponds to the CO
2
(CO
2
-VOC) concentration for which
the air quality is held to be very bad.
SP.1,2% SP.2,3% and Δ values depend on the values of both parameters
AutoMin ppm
and
AutoMax ppm
according to the following formulas:
none
(Default value) no device is installed for the automatic operation of the fan speed.
AutoMin%
This parameter is only available if the auto parameter is set on ext. signal or UR sensor. It can take values between
0 and 99% (1% steps) with the following limit: AutoMin%<AutoMax%
For a unit equipped with variable speed fans:
If auto ext. signal
corresponds to the input signal percentage value for which fans turn at the minimum speed; below
this value, fans remain set at the minimum speed. For instance, the value AutoMin% 030 corres-
ponds to a 3V (30% of 10V) input signal.
If auto UR sensor
corresponds to the (percentage) relative humidity for which fans turn at the minimum speed; below
this value, fans remain set at the minimum speed.
EN