112
0.40
It is the value of the proportional coefficient relevant to the detected flow.
Tau Dp sec.
This parameter is only available for constant pressure units with control on one flow (Factory menu).
030
It is the value of the integral time relevant to the detected flow.
Max Flow
This parameter is only available for units with constant pressure (Factory menu).
20000 m3\h
Flow Exhau.
= XXX%
Flow supply
This parameter is only available for units with constant pressure with control on both flows (Factory menu).
074%
ĺ
135%
Default value 100%, expresses, as a percentage, the desired ratio between the exhaust fan flow
and the supply fan flow, which creates an imbalance between the flows of both flows.
Kp Flow Sup
This parameter is only available for constant flow units with control on both flows (Factory menu).
0.40
It is the value of the proportional coefficient relevant to the input flow.
Tau Flow
Su s
This parameter is only available for constant flow units with control on both flows (Factory menu).
030
It is the value of the integral time relevant to the input flow.
Kp Flow Exh
This parameter is only available for constant flow units with control on both flows (Factory menu).
0.40
It is the value of the proportional coefficient relevant to the return flow.
Tau Flow
EX s
This parameter is only available for constant flow units with control on both flows (Factory menu).
030
It is the value of the integral time relevant to the return flow.
Kp Flow
This parameter is only available for constant pressure units with control on one flow (Factory menu).
0.40
It is the value of the proportional coefficient relevant to the detected flow.
Tau Flow sec
This parameter is only available for constant pressure units with control on one flow (Factory menu).
030
It is the value of the integral time relevant to the detected flow.
Adjust zero
Dp/Flow
Le capteur de pression peut être réinitialisé grâce à ce paramètre.
Cette opération doit s’exécuter quand le système est éteint, il est également préférable d’effectuer cette démarche
de manière régulière afin de corriger toute erreur de lecture.
Fan exhau.=
XXX%
This parameter is available if the control is set to run variable speed fans (Factory menu).
Fan supply
074%
ĺ
135%
Default value 100%, it expresses, in a percentage format, the desired ratio between the exhaust fan
speed and the input fan speed that generates an imbalance between the air flows.
The maximum speed that can be set in the main window will always be 100%, what changes is the
minimum speed value that can be set by the final user (see Max. speed).
Ti (in)min
This parameter is available if the control is set to run an electric or modulated water-based after heating system
(no water-based cooling).
16
ĺ
20
Default value 18, it is expressed in degrees centigrade; it is the minimum value of the range in which
the control keeps the temperature of the supply air flow
Ti min inv.
This parameter is available if the control is set to run a modulated water-based air after-treatment system.
16
ĺ
20
Default value 18, it is expressed in degrees centigrade; it is the minimum value of the range in which
the control keeps the temperature of the supply air flow in heating mode (Parameters menu, Winter
season):
Ti min est.
This parameter is available if the control is set to run a modulated water-based air after-treatment system (heating/
cooling).
20
ĺ
24
Default value 22, it is expressed in degrees centigrade; it is the minimum value of the range in
which the control keeps the temperature of the supply air flow in cooling mode (Parameters menu,
Summer season):
TI
ࣅ
[(TI (in)min est. TI (in)max)]