66
EN
When this menu item is selected and OK is pressed, unit control parameters are automatically assigned default values:
Time table
Program valid Monday through Friday
Time period
Fan speed/flow/pressure
Air after-treatment status:
(ON/OFF)
C1
00:00
ĺ
06:29
Medium
OFF
C2
06:30
ĺ
07:59
Medium
ON
C3
08:00
ĺ
11:29
Low
ON
C4
11:30
ĺ
12:59
High
ON
C5
13:00
ĺ
17:59
Low
ON
C6
18:00
ĺ
21:59
High
ON
C7
22:00
ĺ
00:00
Medium
OFF
C8
Not used
—
—
Program valid Saturday and Sunday
Time period
Fan speed/flow/pressure
Air after-treatment status:
(ON/OFF)
C1
00:00
ĺ
07:29
Medium
OFF
C2
07:30
ĺ
07:59
Medium
ON
C3
08:00
ĺ
11:29
Medium
ON
C4
11:30
ĺ
12:59
High
ON
C5
13:00
ĺ
17:59
Medium
ON
C6
18:00
ĺ
21:59
High
ON
C7
22:00
ĺ
00:00
Medium
OFF
C8
Not used
—
—
Speed levels
Low speed
OFF
Medium Speed
030%
if the unit is equipped with variable speed fans.
1
if the unit is equipped with 3-speed fans.
Auto
if the unit is equipped with a CO
2
or relative humidity probe, or
is controlled through a 0-10V external signal.
0200 m3\h
if it is a constant flow unit with cop/cav kit. This value
also depends on the settings in the factory menu based on the perfor-
mance of the unit.
010 Pa
if it is a constant pressure unit with cop/cav kit. This value
also depends on the settings in the factory menu based on the perfor-
mance of the unit.
High Speed
065%
if the unit is equipped with variable speed fans.
2
if the unit is equipped with 3-speed fans.
Auto
if the unit is equipped with a CO
2
or relative humidity probe, or
is controlled through a 0-10V external signal.
20000 m3\h
if it is a constant flow unit with cop/cav kit. This value
also depends on the settings in the factory menu based on the perfor-
mance of the unit.
1000 Pa
if it is a constant pressure unit with cop/cav kit. This value
also depends on the settings in the factory menu based on the perfor-
mance of the unit.