6
2.2 On-site transportation
The unit is mounted on cross members. During transport by forklift, make sure forks are long enough so that all support struts are resting upon them.
Be careful not to damage the cross members when passing the forks under the unit (allow a minimum space of 350mm).
Support struts
Cross members
Fork separation 350mm min.
Handling using slings: Use the lifting bars placed inside the cross members. The bars' fl exural rigidity must be appropriate for the weight of the unit.
Place the sling loops around the lifting bars and place spacers above the unit so as not to damage the casing. See Diagram below.
Separators
Sings
Lifting bars
2.3 Parts included in the package
2.3.1 Air input temperature probe
A 3m long wire probe is provided, connected inside the lower connection box . It must be placed in the air input duct. The probe is equipped with a
metal support rod and a PG 9 cable gland, for installation see section 1.6.
2.3.2 Documentation envelope
All documents relating to using the unit are located behind the black door.
A SD card with a USB adapter containing the control and software confi guration instructions are included in the documentation envelope.