MANUAL VERSION (FIG. I)
• Trip
- manual:
press the white button (see diagram page 12, number 6).
- automatic control:
any temperature above 70°C trips the fuse mounted on all MINISONE (obliga-
tion under NF S 61-937-5 and NF EN 1366-2).
• Reset
- manual:
use a screwdriver without removing the cover.
• Signalling
The closed position contacts (FCU1)
indicate the safety position of the
damper (i.e. closed), the open position
contacts (DCU1) indicate the standby
position (open).
These contacts are illustrated as
inactive, use the NO terminals on the
contacts to close a signalling circuit
(or light lamps for example). They are
available as an option (see page 16).
MOTORISED VERSION WITH BELIMO MOTOR (FIG. II)
• Trip
- manual:
Use the switch on the top of the thermal sensor.
- automatic:
using the thermal sensor when the temperature exceeds 72°C.
- remote control:
by cut-off of electric power.
• Reset
- motorised:
remotely by energizing the reset motor. The motor stops automatically. Electric reset
lasts approximately 60 seconds.
- pre-mounting test:
use the handle supplied and turn clockwise until it stops.
• Signalling
The closed position contacts (FCU1)
indicate the safety position of the
damper (i.e. closed), the open position
contacts (DCU1) indicate the standby
position (open).
These contacts are illustrated as
inactive, use the NO terminals on the
contacts to close a signalling circuit (or
light lamps for example) - see page 16.
ACTIVATION
Fig. I
Fig. II