21
English
English
TECHNICAL DETAILS
Control mechanism
MINISONE Auto-control
manual reset
MINISONE with 24 V DC
reset motor
MINISONE with 230 V AC
reset motor
Type of product
Auto-control fire damper
Remote-control fire damper Remote-control fire damper
Certificate
CE, NF
CE
CE
Control mode
Automatic: fuse at 70°C
• Automatic: thermal sensor
at 72°C
• Remote control: cut-off
power supply
• Automatic: thermal sensor
at 72°C
• Remote control: cut-off
power supply
Safety options
Safety position contact
(closed)
Standby position contact
(open)
Standby position contact
(open)
Additional function
FCU1 + DCU1 (SN2) as
standard
FCU1 + DCU1 (SN2) as
standard
Fire resistance ratings
• Pressure 500 Pa:
- EI60 (Ve i o) S: range
up to Ø 315: Mounted in
110 mm solid concrete
wall
- EI60 (Ve i o) S: range
up to Ø 315: Mounted
in 100 mm solid aerated
concrete wall
• Pressure 500 Pa:
EI60 (Ve i o) S: range
up to Ø315: Mounted in
standard 98/48 lightweight
partition wall
• Pressure 500 Pa:
- EI60 (Ve i o) S: range
up to Ø 315: Mounted in
110 mm solid concrete
wall
- EI60 (Ve i o) S: range
up to Ø 315: Mounted
in 100 mm solid aerated
concrete wall
• Pressure 500 Pa:
EI60 (Ve i o) S: range
up to Ø315: Mounted in
standard 98/48 lightweight
partition wall
• Pressure 500 Pa:
- EI60 (Ve i o) S: range
up to Ø 315: Mounted in
110 mm solid concrete
wall
- EI60 (Ve i o) S: range
up to Ø 315: Mounted
in 100 mm solid aerated
concrete wall
• Pressure 500 Pa:
EI60 (Ve i o) S: range
up to Ø315: Mounted in
standard 98/48 lightweight
partition wall
Airtight quality as per
EN 1751
Class B
Class B
Class B
Direction of fire propagation Indifferent
Indifferent
Indifferent
Direction of air circulation
Indifferent
Indifferent
Indifferent
Direction of assembly
Indifferent
Indifferent
Indifferent
Type of installation
Flush-mounted in wall
Flush-mounted in wall
Flush-mounted in wall
Dimensions
Ø 100 mm to 315 mm
Ø 100 mm to 315 mm
Ø 100 mm to 315 mm
Uc voltage
24 V DC
230 V AC
Power
2.5 W (5 W for the rearming) 3 W (6 W for the rearming)
Endurance
300 cycles
-
-
Prohibition
Remote reset prohibited
Nominal conditions/
sensitivity of activation:
• sensor load capacity
• sensor response
temperature
Compliant
Compliant
Compliant
Response time: closure time Compliant
Compliant
Compliant
• Sustainability of response
time: sensor response
to temperature and load
capacity
• Sustainability of
operational reliability:
opening and closing cycles
Compliant
Compliant
Compliant