HINGED FILTER ACCESS
1-3/4"
Page 2 | FSVS140
ELECTRICAL DATA
115 V, 60 Hz, 41 W, 0.34 A, 2200 RPM
Above ratings are intended for sizing electrical wiring only.
Actual consumption will be lower.
Dimensions & Performance
FRONT VIEW
TOP VIEW
WARRANTY
3
YEARS
FSVS140 ELECTRICAL AND AIRFLOW PERFORMANCE*
Model
Watts at
0.2" Ps
CFM vs. Static Pressure
0.0"
0.2"
0.4"
0.6"
0.8"
1.0"
FSVS140
32.3
178
140
110
79
51
22
*Certified airflow rating at 0.2” w.g. is derated from actual test results per HVI Certification
procedure 920.
The HVI Certified Rate for FSVS140 = 140 CFM.
Heavy-gauge G90
galvanized steel construction
MERV 8 pleated filter
or A+2000 electrostatic
permanent filter options
Drop-down hinged
motor and filter
access panels for
easy service
High-efficiency motor
meets ENERGY STAR
performance criteria
Internally
insulated
with acoustic
vapor barrier
insulation
REFERENCE RDF INSTALLATION SUPPLEMENT FOR ADDITIONAL
INSTRUCTIONS AND WARRANTY INFORMATION.
Ducting the Fan
The ducting from this fan to the outside of the building has a strong effect
on the air flow, noise and energy use of the fan. Use the shortest, straightest
duct routing possible for best performance, and avoid installing the fan
with smaller ducts than recommended. Insulation around the ducts can
reduce energy loss and inhibit mold growth. Fans installed with existing
ducts may not achieve their rated airflow.
Use ductwork of a diameter that is the same as or greater than the
diameter of the duct connectors on the fan.
Filters
The FSVS is designed to house a disposable-type 1” pleated MERV 8
filter to comply with ASHRAE 62.2 and ENERGY STAR standards. Another
compliant filter option is the permanent, washable, electrostatic type.
Performance
Fan airflow and energy performance shall be tested in accordance with
HVI procedures.