2.8. Hydraulic connection
2.8.1. Connecting condensates general
All condensate evacuations must be connected without fail to a water trap (plate heat exchanger and cold coil optional). These water traps are delivered
with every unit, in a box placed in the unit. The water traps with diaphragm are used to combat the negative pressure prevailing in the equipment, so
that condensates can be evacuated or to prevent air leaking from the u
Water trap with diaphragm
Condensate
evacuation direction
nit.
Watch out
for the risk of frost in winter, plan to insulate the water trap and the evacuation manifold if they are in an unheated atmosphere.
2.8.2. Connecting condensates heat exchanger
Our condensate trays are equipped with an evacuation pipe crossing the floor. This comprises a plughole and a PVC hose Ø32. The water trap with
diaphragm is delivered in the box of separate parts. Connect the water trap with diaphragm to the evacuation hose.
Caution:
Respect the condensate evacuation direction indicated by an arrow on the connector.
Plughole
PVC hose Ø 32 mm
Water trap with diaphragm
Ø 32 mm female