6
Handling with slings: use handling bars placed in the cross bars. The rigidity at the sag of bars must be adapted to the weight of the crate. Place the
sling buckles around the handling bars and place spreaders above the unit to avoid damaging the structure. See diagram below.
mounted. See Section 0 for the fitting of accessories.
Caution:
if a water coil is fitted, condensates are discharged in the air intake leg! Make sure the hose is not damaged when inserting the bars.
Space required for servicing: it must be possible to open the two side doors at least 90° so that filters can be replaced.
Slings
Four spreaders
Handling bars
2.3. Parts supplied with the unit
A box is placed in the unit containing a water trap with diaphragm to evacuate condensates from the heat exchanger. Depending on the options
chosen, a 3-way valve and a servomotor and a water trap with diaphragm for condensate evacuation from cold coils are all supplied. Depending on the
options chosen, probes, transparent tubes and pressure taps are pre-connected, on stand-by in the side rail air supply side.
All the notices for the use of the unit are behind the new air filter access door. An SD board with USB adapter, containing the software setting and
configuration, is provided in one of the pockets.
A water trap with diaphragm is placed in the box and must be installed after the heat exchanger condensate evacuation hose. See Section 2.8.1.
An air intake probe is connected to the control board, placed on stand-by in the side rail air intake side. See Section 2.6 for the installation.
2.3.1. Water coil option
2.4. Installation of the unit
2.4.1. General information
Mount the unit's legs on a flat, stable surface (flat ground for condensates).
It is advisable to install an anti-vibration device between the unit's legs and the frame (e.g. studs or carpet) and between the connections and the
aeraulic ductwork (e.g. flexible sleeve).
When installing the unit and connecting ducts and electric cables, make sure not to obstruct the access points so that the internal functional
components can be extracted easily and the unit can be connected electrically.
700 mm
700 mm