Warning:
P
rotection levels vary based on
the Z
one spa is placed in. See the below scheme:
Above figure: Zone dimensions of swimming pools and paddling pools
Note: The measured zone dimensions are
not
limited by walls and fixed partitions.
•
A
permanent
grounded bond consisting of a minimum 8-guage
solid
copper
conductive
wire is required
between spa control panel grounding terminal and any metal surface located in Zone 1.
•
No metal surfaces or outside electrical devices may be present within Zone 0 for any reason.
•
All bonded connections must be fully-conductive and grounded.
•
Electrical equipment shall have at least the following degrees of protection:
o
Junction boxes shall not be installed in Zones 0 and 1
.
o
In Zones 0 and 1, no switch
es
, lights
or
any
other
electrical
components
shall be
present
.
o
The transformer must be located outside
Z
one 1.
We decline liability for any damage or accident derived from any use of this product
which is not in conformity with the instructions contained in this booklet.
Please consult a licensed electrician for further electrical installation guidelines,
or in placement scenarios not specifically mentioned in this manual.
CORRECT DISPOSAL OF THIS PRODUCT
This marking indicates that this product should not be disposed with other
household wastes throughout the EU. To prevent possible harm to the
environment or human health from uncontrolled waste disposal, recycle it
responsibly to promote the sustainable reuse of material resources. To
return your used device, please use the return and collection systems or
contact the retailer where the product was purchased. They can take this
product for environmental safe recycling.
Copyright 201
9
ALEKO. All rights reserved. No part of this manual may be reproduced or transmitted in any form
or by any means without the express written permission of ALEKO.
ALEKO Inflatable Spas, website: www.AlekoProducts.com
(Read this
entire
manual before operation)
ELECTRICAL
PROTECTION LEVEL
12