31
Start-up Type 8692
Type 8692, 8693
Circular plug M8 - 4-pole (process actual value) - Type 8693
input
type
17)
pin
Wire
color
18)
configuration
switch
4 – 20 mA
- internally
supplied
1
2
3
4
brown
white
blue
black
+ 24 V transmitter supply
Transmitter output
GND
Bridge after GND
Switch
on left
4 – 20 mA
- externally
supplied
1
2
3
4
brown
white
blue
black
not assigned
Process
not assigned
Process actual -
Switch
on right
Frequency
- internally
supplied
1
2
3
4
brown
white
blue
black
+ 24 V sensor supply
Clock input +
Clock input - (GND)
not assigned
Switch
on left
Frequency
- externally
supplied
1
2
3
4
brown
white
blue
black
not assigned
Clock input +
Clock input -
not assigned
Switch
on right
Pt 100
(see infor-
mation
below)
1
2
3
4
brown
white
blue
black
not assigned
Process actual 1 (current feed)
Process actual 2 (GND)
Process actual 3 (compensation)
Switch
on right
Tab. 17: Circular plug M8 - 4-pole (process actual value) - Type 8693
For reasons of wire compensation connect the Pt 100 sensor
via 3 wires. Always bridge Pin 3 and Pin 4 on the sensor.
11. sTarT-uP TyPe 8692
To start up the positioner, the basic settings (operating mode of the
actuator and input signal (standard signal)) must still be specified
and the
X.TUNE
function must be run to adjust the device to local
conditions following installation.
The operating mode of the actuator is preset at the factory
with the process valve mounted.
For a detailed description of the start-up and control of type
8692 refer to the operating instructions of type 8692.
11.1. safety instructions
Warning!
risk of injury from improper operation!
Improper operation may result in injuries as well as damage to the
device and the area around it.
• Before start-up, ensure that the operating personnel are familiar
with and completely understand the contents of the operating
instructions.
• Observe the safety instructions and intended use.
• Only adequately trained personnel may operate the equipment/
the device.
english