14.7 230V Triac output
The 230V electrical output can be configured as a pulse
function. For example it can be used to shortly activate an
electrical drain valve.
In this configuration, you can program pulse duration,
day, week or special days you want this to happen.
For example each Sunday at 10h00 for 5 seconds.
See
7.9 230V Triac menu
.
Connected device must not exceed 230VAC 1A.
Picture 28
14.8 Relay 1 and 2 contacts
Relay 1 can be NO (normally open) or NC (normally closed).
Relay 2 is always NO (normally open).
Connect the relay 1:
Operating
mode
Connections on PCB bottom
terminal
NO
C-NO (25-24)
NC
C-NF (25-26)
Connect relay 2 to the controller terminal 13(IN6) and 14 (OUT6).
See
4.2 Electrical wiring diagram
.
If using 230V phase through this contact, do not exceed 2A load.
14.9 Remote Control contact
The AquaFirst can be operated by a remote controller. To enable that connect a volt free contact between BI1
and GND.
Wire terminal name
Wire terminal number
BI1
33
GND
31 or 37
See
4.2 Electrical wiring diagram
.
NOTE
: When the contact is open, the unit operates normally. If it is closed, primary and secondary pump are
stopped and valves get a 0% (0 volt) signal. The unit is in standby but the controller display remains activated.