AHE00045EN 1904
5
Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB.
Alfa Laval reserves the right to change specification without prior notification.
2.3 Options
• Electric defrost (E)
For cold rooms with room temperatures below 4 °C and frost build-up is likely, the application of
a defrosting system is advised. Electric defrost for Optigo CS consists of stainless steel heater
elements mounted against the bottom plate of the coil. The defrost element can be accessed
after opening the driptray. The defrost element are connected to separate terminals in the termi-
nal box. Electric defrost is mounted as default for 7 mm models, optional as a separate kit for 4
mm models.
Optigo model
Watt
Power supply
CS201
410
230/50-60/1
CS202
890
230/50-60/1
CS301
580
230/50-60/1
CS302
1110
230/50-60/1
CS303
1640
230/50-60/1
CS304
2170
230/50-60/1
CS305
2700
230/50-60/1
2.4 Code description
CS E
H 20 2
B
S
230V
BO
AL
E
CB - AL 7.0 CU
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
Commercial unit cooler - slim line
2
Refrigerant system (E=HFO/HFC DX, X=CO
2
DX)
3
Fan speed (H=high speed, L=low speed)
4
Fan diameter (20=200, 30=300 mm)
5
Number of fans (1 to 5)
6
Tube rows code (B, C)
7
No. of phases (S=1)
8
Motor voltage
9
Packing (BO=box)
10
Casing material (AL=epoxy coated aluminium)
11
Defrost system (E=electric defrost, blank=air defrost)
12
Connection box (CB)
13
Fin material (AL=aluminium)
14
Fin spacing (4.0, 7.0 mm)
15
Tube material (CU=copper)
Summary of Contents for Optigo CS