5.6 Electrical connections
The following data determine which connection diagram is to be selected and respected for electri-
cal installation:
• Heat exchanger model indication
• Fan motor type
• Electrical options
Electrical connection diagrams are available for download on
When in doubt always contact your local Alfa LU-VE representative for assistance.
5.5 Drain line
The drain line diameter must be at least the size of the driptray drain diameter and should be laid
with an adequate slope. For room temperatures below 0° C drain line insulation and an internal or
external heating element are required to prevent freezing.
Tighten drain connection by using two wrenches.
Keep wrenches firmly to not strain on connection
welding.
A syphon must be installed on the drain line,
outside the cold room.
Optional drain kit for PVC click-on connection
including adapter, O-ring and 40 mm 45° PVC
connection, freely adjustable into either horizon-
tal or vertical position.