6
Figure 1
- the smoke can be directly headed in the smoke pipe (flue) only if it has a cross section up to 15x15cm or a
diameter up to 15 cm and if it has a cover for check and cleaning.
-
If the flue has bigger cross section
than 15x15cm or a diameter bigger than 15cm, you can perform eventual
regulation of increased draft (reduction) in the flue in three manners:
1.If the flue bottom has an opening for cleaning, it should be partially open.
2. Insert a steel pipe in the flue, with a diameter of 10cm if you own elements for such correction of the flue.
3. By regulation of certain parameters in the stove. This regulation may be performed only by an authorized service
of Alfa Plam.
− Make sure that the connection to the house flue is properly sealed.
- Avoid contact with an easily burning material (such as wooden beams) and in all cases it is necessary to insulate
them with fireproof material (see figure 2).
A) Mineral wool
B) Steel pipe
C) Partition panel.
The stove is made for connection to a flue with a flue pipe with a diameter of 80mm. If the standard flue is not used,
but a new flue is made, or if you are changing the existing one, use insulated stainless pipe (double wall) with a
diameter according to the given table 1. Flexible pipes are not allowed.
TYPE OS SYSTEM
DIAMETER mm
SYSTEM ASSESSMENT
Pipe with a length of less than 5 m
80
Acceptable
Pipe with a length of more than 5 m
100
Compulsory
Installation in places above 1.200 masl
100
Recommendable
Table 1