Introduction
Algas-SDI Operation and Maintenance Manual – P/N – 54000
1-3
DIRECT FIRED VAPORIZER SPECIFICATIONS:
B
URNER INPUT
176,900 BTU/hr (51.8 kW) per burner
GAS CONSUMPTION:
Approximately 1,000 BTU/hr (0.3 kW) per gallon (3.79 liters) of propane vaporized
TOTAL BURNER INPUT
160H
:
176,900 BTU/hr (51.8 kW)
320H
:
353,800 BTU/hr (103.6 kW)
480H
:
530,700 BTU/hr (155.4 kW)
640H
:
707,600 BTU/hr (207.2 kW)
800H
:
884,500 BTU/hr (259.0 kW)
THERMOSTAT SUPPLY REGULATOR PRESSURE
*
:
15-18” W.C. (37.3 – 44.8 mbar)
B
URNER PRESSURE**
: 9” W.C. (22.4 mbar)
PI
LOT BURNER:
2,200 BTU/hr (0.64 kW)
NOMINAL OPERATING TEMPERATURE**
*
:
140 to 160
°
F (60 to 71ºC)
* Regulator Gas Pressure measured between burner regulator and thermostat at the drip leg. Regulator
supply pressure may vary in order to obtain 9” W.C. (22.4 mbar) at the burner. See “Adjusting burner input
pressure” on page 4-21.
** Burner pressure measured at the burner pressure test port. See “Adjusting burner input pressure” on
page 4-21.
*** Operating Temperature depends on ambient temperature, thermostat settings, and operating pressures.