Troubleshooting
Algas-SDI Operation and Maintenance Manual – P/N – 54000
5-31
TROUBLESHOOTING TREE #5
VAPOR SERVICE PRESSURE DROPS
IS THE BURNER
OPERATING?
CHECK
OPERATION
YES
NO
ADJUST BURNER
PRESSURE
REGULATOR
OK
SEE TROUBLESHOOTING TREE #3:
MAIN BURNER WILL NOT LIGHT
WILL NOT ADJUST
CHECK FOR
MINIMUM OF
6psig (0.4 bar) AT
REGULATOR
REPLACE
REGULATOR
REPAIR PRESSURE
SOURCE
PRESSURE
OK
CHECK THE
THERMOSTAT PORT
OUTLET PRESSURE
REFER TO PAGE 1-3
OK
LOW/HIGH
SET THERMOSTAT FOR
HIGHER TEMPERATURE
CHECK IF BURNER
TIPS CLOGGED
(ORANGE/NO
FLAME)
NO
REPLACE
THERMOSTAT
YES
CLEAN
BURNER TIPS
AND ORIFICES
REPLACE
THERMOSTAT
CHECK
OPERATION
DOES NOT
FUNCTION
OK
PRESSURE
LOW
NOTE
:
SERVICE PRESSURE WILL DROP IF THE
DEMAND EXCEEDS VAPORIZER’S CAPACITY. THE
FOLLOWING TROUBLESHOOTING TREE ASSUMES
THAT THE LOAD ON THE VAPORIZER IS LESS THAN ITS
MAXIMUM CAPACITY.