ASDI Operations and Maintenance – TX Models – P/N: 52368
6-34
TREE # 2C
Liqui-SAFE VALVE DOES NOT TRIP
RED
IS THERMOCOUPLE
MOLEX LOOSE OR
DISCONNECTED?
IS HIGH TEMP.
LIMIT
REACHED?
PRESS RED RESET BUTTON TO
RESTART VAPORIZER.
IF PROBLEM REOCCURS THEN:
1. CHECK BOARD SETPOINT
2. CHECK FOR SUFFICIENT
THERMAL GREASE IN
THERMOWELL
3. CHECK THERMOCOUPLE
INSERTION DEPTH
4. REMOVE DRAIN PLUG AND
CHECK FOR HEAVY ENDS
IF THE ABOVE ACTIONS DO NOT
FIX THE PROBLEM THEN
CONTACT ASDI OR GO TO NEXT
STEP IF FLOAT OR PRESSURE
SWTITCH ARE INSTALLED.
YES
NO
NO
YES
RECONNECT LOOSE OR
DISCONNECTED MOLEX
PRESS RED RESET BUTTON TO
RESTART VAPORIZER
IF THE ABOVE ACTIONS DO NOT
FIX THE PROBLEM THEN GO TO
THE NEXT STEP
IS FLOAT
SWITCH OR
PRESSURE
SWITCH
OPEN?
1. ASSESS SYSTEM
CAPACITY
2. PERFORM SOLENOID
VALVE LEAK TEST.
3. CHECK WIRING.
4. CHECK FUSE LINKS.
IF THE ABOVE ACTIONS
DO NOT FIX THE
PROBLEM CONTACT
ASDI.
REPLACE TEMP.
CONTROLLER.
RESTART
VAPORIZER
NO
YES
OPTIONAL