ASDI Operations and Maintenance – TX Models – P/N: 52368
6-40
Solenoid
Valve
Electrical
Test
NOTE
A multimeter is required for the following test.
CAUTION
Turn off electrical power at the disconnect before performing this
procedure.
Open the electrical housing at the vaporizer base. Disconnect the 2-PIN Molex
plug connector and measure resistance between the pins. You should measure
approximately 3 ohms. If not, replace the solenoid coil.
Figure 16 – Solenoid Valve Electrical Test
RESISTANCE SHOULD BE
APPROXIMATELY 3 OHMS
1. DISCONNECT
SOLENOID MOLEX
FROM MAIN HARNESS
2. MEASURE
RESISTANCE
3. RECONNECT WHEN
FINISHED