background image

Remove screen and clean.

Inspect pilot for proper flame.

Inspect for proper flame.

Check for signs of corrosion and replace
any missing caps.

Check entire enclosure, louvers and
vent cap for debris.

Strainer

Pilot Burner Assembly

Main Burner Assembly

Relief Valves

Enclosure

Service to Perform

Items to Service Monthly

Monthly Check List

Check thermostat for proper operation.
Replace if needed.

Check thermocouple position in pilot
and verify proper millivolt output.

Replace valve seat, spring and O-ring
using Kit # 3-0016.

Clean piston and replace the spring and
O-ring using Kit # 3-0017.

Check flues for holes or excessive scale.
Remove debris. Check bottom of the
heat exchanger for pitting. Replace if the
pitting is in excess of 0.125".

Check for proper flame. Clean debris and
check air supply. Clean orifices as needed.

Thermostat

Thermocouple

Liquid Inlet Valve

Capacity Control Valve

Heat Exchanger

Main Burner

Service to Perform

Items to Service Annually

Annual Check List

Maintenance Schedule

Vaporizer Repair and Maintenance Guide

FLAMMABLE GAS

Vaporizers and ancillary equipment should be serviced ONLY by trained 
and fully qualified personnel. This equipment operates with LP gas which 
is flammable and under pressure. Inherent hazards exist and a thorough 
understanding of the equipment is required for safe maintenance.

Regular scheduled maintenance on vaporizers is a must for trouble free operation. The 
suggested schedules listed above should be used as a guide. Certain installations and 
situations will require more stringent inspection and repair.