MONITORED ENTRAPMENT PROTECTION DEVICE CONNECTIONS

Ÿ

There  are  2  types  of  sensors  that  can  be  connected  to  the  gate  operator  for  UL  325  monitored  entrapment 
compliance: non-contact sensors (photo eye) and contact sensors (edge sensors).

Ÿ

Monitored  entrapment  protection  devices  use  4  wires  to  connect  to  the  board.  From  the  device,  connect  the 

RELAY  COMMON

  to  the  board 

COMMON

  and  the 

NORMALLY  CLOSED

  relay  contact  to  the  assigned 

MON_OPEN 

or 

MON_CLOSE

 input. Connect the power wires to the 

COMMON

 and 

MON-24VDC.

Ÿ

IMPORTANT:

 You must use the MON-24VDC to properly monitor entrapment protection devices. Do not use the 

24 VAC terminal on the board’s terminal strip.

Ÿ

Please refer to the device manufacturer wiring instructions for details, making sure to follow the normally closed 
wiring directions. Some devices may work on monitoring interfaces other than normally closed.

Ÿ

Should there be a need for more than 1 entrapment protection device for each direction, use a multi-input module 
from Miller Edge (model: MIM-62).

MON_CLOSE 

(LED will indicate when an obstruction is detected or device is not present) 

This  input  is  only  for  the  monitored  entrapment  protection  device  for  the  close 
direction.  When  the  gate  is  closing,  it  will  open  to  the  full  open  position  if  an 
obstruction is sensed and resets the automatic close timer. This input does nothing 
in  the  opening  direction.  If  a  device  is  not  connected  or  it  senses  a  fault 
(MON_FAULT LED will turn on), the operator will only work with a constant pressure 
actuated switch.

MON_OPEN 

(LED will indicate when an obstruction is detected or device is not present)

This  input  is  only  for  the  monitored  entrapment  protection  device  for  the  open 
direction.  When the gate is opening, it will reverse for 2 seconds and stop if it senses 
an obstruction.  This input does nothing in the closing direction.  Upon power up, if a 
device  is not detected,  the operator  will  assume  that one  is not required  for the 
opening  direction.    If  a  device  is  connected  and  the  board  detects  a  fault 
(MON_FAULT LED will turn on), the operator will only work with a constant pressure 
actuated switch.

COMMON

STOP CMD

COMMON

MON-12VDC

MON_OPEN

MON_CLOSE

CLOSE

PHOTO EYE

COM

N.C.

N.C.

OR

COM

CLOSE

EDGE

OPEN 

PHOTO EYE

COM

N.C.

N.C.

OR

COM

OPEN
EDGE

PCB model: T24PCB

O

U

R

3

6

B

S3

O

U

R

3

6

B

S3

O

U

R

3

6

B

S3

ALL-O-MATIC INC.

<ENG.      ESP.>

CMX-309FB  C

8.0000 M

535202

CMX-309FB  C

8.0000 M

535202

CMX-309FB  C

8.0000 M

535202

1     2    3    4     5    6     7    8

-----------------------OPEN------------------------

5

5

MOT

OR 1

MOT

OR 2

SINGLE/DUAL

IN/OUT

24V AC
LINE IN

EXTERNAL

S/N:

DATE:

O

U

R

3

6

B

S3

O

U

R

3

6

B

S3

O

U

R

3

6

B

S3

OPEN 

ERD

CLOSE

ERD

TIMER

MON_12/24VDC

MON_CLOSE

MON_OPEN
STOP CMD

COMMON

COMMON

Summary of Contents for TORO 24

Page 1: ...SWING GATE OPENER INSTALLATION MANUAL TORO 24 UL325 Compliant Compliant Compliant UL991 CSA C22 2 Canada L I S T E D US Compliant Copyright 2017 all o matic inc www allomatic net WWW ALLOMATIC NET...

Page 2: ......

Page 3: ...Direction Setting 16 Programmable Relay 17 Electronic Reversing Device ERD Adjustment 18 Timer Adjustment and Radio Setting 19 Dip Switch Functions 20 LED Diagnostics 21 WIRING ACCESSORIES TO CONTROL...

Page 4: ...the gate is not moving It is advised that the power be turned off Always keep people and objects away from the gate No one should cross the path of a moving gate The gate operator must be tested month...

Page 5: ...minimum force setting that will allow for reliable gate operation Install the operator inside the fence line Do not install the operator on the public side of the fence line Install a proper electric...

Page 6: ...cted access locations not servicing the general public and where unauthorized access is prevented via supervision by security personnel THE SIX TYPES OF OBSTRUCTION SENSING SYSTEMS TYPE A Inherent ent...

Page 7: ...e phase 4 amps 230 VAC single phase 2 amps or 12 24 VDC solar panel up to 80 watts Duty Cycle Continuous Temperature Range 40 to 160 Gear Box Ratio N A Dimensions Fully retracted arm 38 39 Fully exten...

Page 8: ...D TIMER GATE OPERATOR BACK MOUNTING PLATE BACK MOUNTING BRACKET FRONT GATE BRACKET 2 EMERGENCY RELEASE KEY 2 PIVOT PINS PIVOT PIN SECURE SETSCREW Exit Loop Phantom Loop Safety Loop See side for Jumper...

Page 9: ...se the installation measurements in the chart below If necessary modify the gate construction for best automation performance Before proceeding with the gate operator installation be sure of the follo...

Page 10: ...rformance Before proceeding with the gate operator installation be sure of the following The gate moves open and close freely when on manual The gate hinges are properly positioned and lubricated Ther...

Page 11: ...k mounting bracket to t the geometry and weld the bracket to the steel post or back mounting plate NOTE A custom mounting plate is required for gates that open to the outside See Push to Open installa...

Page 12: ...r to gate operation The operator cycles power to the external entrapment protection device and checks for device signals If the operator does not receive the correct feedback from the device the gate...

Page 13: ...it point of the loop saw cut to the gate operator Twist loop wires 6 turns per foot as shown below Improper twisting of wires can cause loop issues When using an inside and outside safety loop loops m...

Page 14: ...gle length wire NEVER use two wires for the ground Check the local city code for proper earth ground rod type and grounding procedures OPERATORS MUST BE PROPERLY GROUNDED Use a minimum of a 20 amp ded...

Page 15: ...en and close limit switches on the bottom of the gate actuator Step 2 Loosen the limit switch screws to allow the switch to slide Step 3 Make the necessary adjustments to the limit switch Step 4 Tight...

Page 16: ...y before the gate starts moving Adjustable up to 6 seconds MOVING SIGNAL Relay is on and kept active while the gate is in motion ALARM SIGNAL Relay is on when the gate has been tampered with This is u...

Page 17: ...m and press ENTER Use the arrows to select the ACTION and press ENTER to save Use the arrows to set the time for the action and press ENTER to save Set the days you would like the action to take effec...

Page 18: ...tions O U R 3 6 B S 3 O U R 3 6 B S 3 O U R 3 6 B S 3 ALL O MATICINC ENG ESP CMX 309FB C 8 0000 M 535202 CMX 309FB C 8 0000 M 535202 CMX 309FB C 8 0000 M 535202 1 2 3 4 5 6 7 8 OPEN 5 5 MOTOR 1 MOTOR...

Page 19: ...tion and press ENTER If PRE WARN SIGNAL was selected you must set the delay use the up and down arrows to set the pre warn delay and press ENTER to save NOTE An asterisk will appear on the selected fu...

Page 20: ...does not reverse when it hits an obstruction the ERD is not sensitive enough O U R 3 6 B S 3 O U R 3 6 B S 3 O U R 3 6 B S 3 ALL O MATICINC ENG ESP CMX 309FB C 8 0000 M 535202 CMX 309FB C 8 0000 M 53...

Page 21: ...meter is turned counter clockwise all the way O U R 3 6 B S 3 O U R 3 6 B S 3 O U R 3 6 B S 3 ALL O MATICINC ENG ESP CMX 309FB C 8 0000 M 535202 CMX 309FB C 8 0000 M 535202 CMX 309FB C 8 0000 M 535202...

Page 22: ...e will stop The vehicle must get off of the loop before the gate continues to close forcing the second vehicle to present valid credentials This is a true one pass anti tailgating feature to be used w...

Page 23: ...a problem with the motor hall sensor feedback Blinks twice every two seconds when a motor overload is detected Blinks three times every two seconds when the game is jammed CLOSE LIM2 ON when the CLOSE...

Page 24: ...itch Push Button Card Reader 5 5 MOTOR 1 MOTOR 2 MON_12 24VDC MON_CLOSE MON_OPEN STOP CMD COMMON COMMON CLOSE CMD C EXIT LOOP DETECTOR KEYPAD OR TELEPHONE PUSH BUTTON OR FIRE BOX CARD READER OR KEY SW...

Page 25: ...pen to the full open position if an obstruction is sensed and resets the automatic close timer This input does nothing in the opening direction If a device is not connected or it senses a fault MON_FA...

Page 26: ..._OPEN COM COMMON POWER COMMON POWER MON_12 24VDC EMX NIR 50 WIRE BOARD TERMINAL BLACK MON_CLOSE OR MON_OPEN WHITE COMMON BLUE COMMON BROWN MON_12 24VDC TRANSMITTER SOLUTIONS R50R UL R32P UL SR33HD SR6...

Page 27: ...additional device The N C contact of the additional device will now go on the SAFETY terminal of the board IMPORTANT Use different frequencies for each loop detector to eliminate interference 12VDC GR...

Page 28: ...ally Open 24V COM CLOSE CMD Stop Common Normally Closed 24V COM STOP CMD CMX 309FB C 8 0000 M 535202 5 5 MOTOR 1 MOTOR 2 MON_12 24VDC MON_CLOSE MON_OPEN STOP CMD COMMON COMMON N C COM OPEN CLOSE STOP...

Page 29: ...outlet plug For Magnetic Lock Wire nut one wire from transformer directly to one wire of the magnetic lock The other wire from transformer will be connected to the board relay plug input and the COM o...

Page 30: ...iver connections l Connect the 2 gray relay wires to the RADIO and COMMON on the radio plug l Connect the black common negative to the COMMON on the radio plug l Connect the red power positive to the...

Page 31: ...the board For a solar installation upgrade the batteries according to usage For information on solar applications solar panel sizes battery size etc please call ALL O Matic O U R 3 6 B S 3 O U R 3 6 B...

Page 32: ...STOP CMD COMMON COMMON EXTERNAL SOLAR SYSTEM INSTALLATION When using an external solar package connect batteries straight into the LINE IN input The batteries will need to be upgraded according to us...

Page 33: ...mpartment forward 2 Insert the key and turn the key clockwise to the unlock position 3 Turn the knob clockwise to release the motor NOTE Make sure the white bar on the knob is on the position opposite...

Page 34: ...ranties are in lieu of all other warranties either expressed or implied andALL O MATIC INC shall not be liable for consequential damage All implied warranties of merchantability and or fitness for a p...

Reviews: