Malfunctions with Indications
2-21
VP-39
Arm Bridge
Overload
Pending
(Warning)
(Parameter 101
bit 13 when
Parameter
630=0)
This Warning will be issued any time the average
armature current exceeds 105% of the nameplate
rating of the armature bridge as specified in
parameter 615 “Rated Arm Brdg I”. It is used to
indicate that the present armature current output
exceeds a predetermined level and continued
operation at this level may cause an Armature
Overload Trip (VP-31).
No action is required for continued operation. However,
depending on the user’s application it may be useful to
monitor this malfunction and take action to reduce the
current output when it occurs.
1. Check encoder signals.
VP-40
Autotune Status
Fault (Soft)
Internal processor error detected during Autotune.
A coast stop will be initiated.
Execute a Clear Fault and attempt normal operation. If the
fault reoccurs, replace Main Control Board.
VP-41
Autotune Logic
State (Soft)
Internal processor error detected during Autotune.
A coast stop will be initiated.
Execute a Clear Fault and attempt normal operation. If the
fault reoccurs, replace Main Control Board.
VP-42
Invalid Feedback
Device
No feedback device or incorrect feedback device
selected.
A feedback device must be selected in parameter 621.
VP-43
Invalid Taper
Speed (Soft)
The speed programmed in parameter 665 “Start
Taper Speed” is less than the speed programmed
in parameter 699 “Autotune Speed”. The taper
speed would have interfered with the Autotune
measurements and the drive faulted as a result.
Program parameter 665 “Start Taper Speed” to a value
greater than parameter 699 “Autotune Speed”. Execute a
Clear Fault and attempt normal operation.
VP-44
Invalid Torque
Mode (Soft)
The torque mode programmed in Parameter 625
“Torque Mode” is incorrect for the commanded
Autotune function. The selected torque mode must
be “1-Velocity Regulate” to perform the VP
measure function.
Select the proper torque mode in Parameter 625 “Torque
Mode”. Execute CLEAR FAULTS and attempt normal
operation.
VP-45
Autotune Start
Timeout (Soft)
If the Autotune measure function is commanded
and the user does not initiate a START command
within 30 seconds, the drive will fault. This guards
against the possibility of the drive being left
unattended in the Autotune command state.
Execute a Clear Fault. The drive is then available for normal
operation or the Autotune measure function.
VP-46
Excess Motor
Rotation (Soft)
The motor shaft moved beyond the allowed rotation
tolerance during the CP measure function. This
indicates that residual flux in the motor allowed
torque to be produced during the armature
measurement.
Execute a Clear Fault and attempt the procedure again with
the motor shaft mechanically locked.
VP-47
CP Not In
Autotune Mode
(Soft)
The CP is not responding to the Autotune request
issued from the VP. Internal communication
between processors has malfunctioned.
Execute a Clear Fault and attempt normal operation. If the
fault reoccurs, replace Main Control Board.
VP-48
Motor Not Up To
Speed (Soft)
The Motor velocity has deviated from the
programmed Autotune Speed as specified in
parameter 699 “Autotune Speed” during the Field
Flux Measure function. The tolerance is
programmed through parameter 709 “Up To Speed
Tolerance”. The Motor velocity must be at the
programmed level before executing the Field Flux
Measure.
Determine why the velocity dropped during the measure
function. It may be due to an excessive load present during
the Field Flux Measure. The available torque is reduced and
it may be necessary to un-couple the load to perform this
measurement. The tolerance may be increased by
increasing the value programmed at parameter 709. Execute
a Clear Fault and attempt normal operation.
Velocity Processor Faults
No.
Name
Description
Recovery