Malfunctions Not Indicated by a Fault
3-27
Table 3.B Logic Supply Levels
If no logic voltages can be detected, check the condition of the fuse
located on the unit power supply. Remove all power prior to checking the
condition of the fuse. If the fuse is not open, replace the unit power
supply.
3.
Before replacing the unit power supply, disconnect and lock-out ALL
incoming voltage sources. Verify that the 3 phase high voltage is
removed from the incoming protection devices, either F1-F3 or the main
circuit breaker CB1. Also verify that the 115V logic supply and
contactor power is removed from TB2-3, 4 and 5. If an external field
supply is used, verify that it is likewise removed by checking TB1-1 & 5.
4.
Verify that the logic supplies also exist on the Main Control Board at the
following test points:
Test Point
Voltage
Low Limit
High Limit
TP1
+12V DC
+11.85V DC
+13.13V DC
TP2
+5.00V DC
+4.98V DC
+5.02V DC
TP4
–12V DC
–11.85V DC
–13.13V DC
Test Point Measurement
TP51
+5V logic supply can be monitored with a DVM. Its signal level should be +5.00
VDC 0.02VDC in respect to TP52
TP52
Digital logic supply common can be monitored with a DVM. Its signal level
should be +0V DC in respect to TE. This signal is used as the reference for
measuring all isolated signals.
TP53
Isolated supply common can be monitored with a DVM. Its signal level should
+0V DC in respect to TE. This signal is used as the reference for measuring all
isolated signals.
TP54
Is12V supply can be monitored with a DVM. Its signal level should be
between 11.85 and 13.13 VDC in respect to TP53.
TP55
+12V logic supply can be monitored with a DVM. Its signal level should be
between 11.85 and 13.13 VDC in respect to TP57.
TP56
-12V logic supply can be monitored with a DVM. Its signal level should be
between 11.85 and 13.13 VDC in respect to TP57.
TP57
Analog supply common can be monitored with a DVM. ITs signal level should
be +0VDC in respect to TE. This signal is used as the reference for measuring
all analog signals.
TP58
+5V isolated supply can be monitored with a DVM. Its signal level should be
+5.00V DC 0.02 VDC in respect to TP53.