background image

 

 

11

 

 

 

 

Terminal Mode to Configure UPS Parameters 

Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS. 

Connect the serial cable to the serial port on the back of the UPS. 

When using PowerChute

®

 

Network Shutdown

 software: 

1.

 

Open a terminal program. Example: HyperTerminal 

 

From the Desktop, go to 

Start

 => 

Programs

 => 

Accessories

 => 

Communication

 

=>

HyperTerminal.

  

2.

 

Double-click on the 

HyperTerminal

 icon.  

 

Follow the prompts to choose a name and select an icon. Disregard the message, “...must 
install a modem,” if it is displayed. Click OK. 

 

Select the 

COM

 port that is connected to your UPS. The port settings are: 

ü

 

bits per second - 2400

 

ü

 

data - bits 8

 

ü

 

parity - none

 

ü

 

stop bit - 1

 

ü

 

flow control - none

 

 

Press ENTER 

3.

 

Example for setting the number of external battery packs: 

Once the blank terminal window is open, follow these steps to enter the number of battery packs: 

 

Press ENTER to initiate terminal mode. Press ENTER multiple times, until the prompt 

User 

Name:

 is displayed. Follow the prompts. Type slowly, waiting until each character appears 

on the screen prior to typing the next character. 

Web/SNMP Card defaults: 

 

User Name:  apc 

 

Password:     apc 

 

Press 1 and ENTER to select Device Manager. 

 

Select the model by entering the corresponding number, then press ENTER. 

 

Press 3 and ENTER to select Configuration. 

 

Press 1 and ENTER to select Battery. 

 

Press 2 and ENTER to change the Battery Settings. 

 

Type in the number of external battery packs (four battery modules per pack), then 
press ENTER. (Number of packs: 1= internal battery module,  
2 = 1 external battery pack, 3 = 2 external battery packs , etc.) 

 

Press 3 and ENTER to accept the changes. 

 

Press ESC multiple times (5) to return to the main menu. 

 

Press 4 and ENTER to log out. 

Summary of Contents for 1609-P10000E

Page 1: ...41063 261 01 1 990 2672 09 2005 Allen Bradley User Manual for 8000 10000 VA UPS 1609 P8000E 8000 VA 200 240 VAC 1609 P10000E 10000 VA 200240 VAC Tower Rack Mount 6U Uninterruptible Power Supply...

Page 2: ...rt Guide Removing the Batteries The unit is heavy To lighten the unit remove the batteries Refer to the unpacking instructions on the carton in which the unit is shipped Environmental Specifications T...

Page 3: ...6 Use appropriate glands to achieve strain relief on the hardwired input and output power cables Input Connection Output Connection optional Wire to L1 L2 Wire to L1A L2A System Wiring Voltage Current...

Page 4: ...3 Installing and Connecting the Batteries and Attaching the Front Bezel...

Page 5: ...up the UPS The battery charges to 90 capacity during the first three hours of normal operation Do not expect full battery run capability during this initial charge period OPTIONS q External Battery Pa...

Page 6: ...ely de energized from a remote location without switching to battery operation see EPO Option TVSS Screw The UPS features a transient voltage surge suppression TVSS screw for connecting the ground lea...

Page 7: ...ch Battery operation is not available while the UPS is in bypass mode see Troubleshooting Fault The UPS detects an internal fault see Troubleshooting Overload The connected loads are drawing more powe...

Page 8: ...ltage display Press and hold the button to view the utility voltage bar graph display After a few seconds the five LED Battery Charge display on the right of the front panel shows the utility input vo...

Page 9: ...nt Alarm Delay After Line Failure 5 second delay 5 second delay 30 second delay At Low Battery Never Mute ongoing alarms or disable all alarms permanently Shutdown Delay 20 seconds 0 20 60 120 240 480...

Page 10: ...bypass operation Output Voltage 208 230 V models 230 VAC 208 230 V models 200 208 220 230 240 VAC Allows the user to select the UPS output voltage while online Output Frequency Automatic 50 3 Hz or 6...

Page 11: ...uit UL CSA standards and an SELV circuit IEC standard Both Class 2 and SELV circuits must be isolated from all primary circuitry Do not connect any circuit to the EPO terminal block unless it can be c...

Page 12: ...nal battery packs Once the blank terminal window is open follow these steps to enter the number of battery packs Press ENTER to initiate terminal mode Press ENTER multiple times until the prompt User...

Page 13: ...outages Use caution when handling heavy battery modules Refer to Installing and Connecting the Batteries and Attaching the Front Bezel for battery replacement procedure reverse instructions for batte...

Page 14: ...or are near the end of service life Charge the battery module s Modules require recharging after extended outages and wear faster when put into service often or when operated at elevated temperatures...

Page 15: ...he battery connectors are fully engaged Weak battery Allow the battery to recharge for 24 hours Then perform a self test If the problem persists after recharging replace the battery Failure of a batte...

Page 16: ...Support Refer to Contact Information below 3 Pack the UPS in its original packaging Pack the UPS properly to avoid damage in transit Never use Styrofoam beads for packaging Damage sustained in transi...

Page 17: ...N Deenergizing Safety If the UPS has an internal energy source battery the output may be energized when the unit is not connected to a utility power outlet To deenergize a pluggable UPS press the OFF...

Reviews: