background image

 

 

13

 

 

 

 

T

ROUBLESHOOTING

 

P

ROBLEM AND 

P

OSSIBLE 

 

C

AUSE

 

S

OLUTION

 

UPS

 WILL NOT TURN ON

 

Batteries are not connected 
properly. 

Check that the battery connectors are fully engaged.  

 button not pushed.  

Press the 

 button once to power the UPS and the connected equipment. 

UPS not connected to utility 
power supply. 

Check that the power cable from the UPS to the utility power supply  is securely 
connected at both ends.  

Very low or no utility voltage. 

Check the utility power supply to ensure proper voltage at the receptacle. 

UPS

 WILL NOT TURN OFF

 

 button not pushed.  

Press the 

 button once to turn the UPS off. 

Internal UPS fault. 

Do not attempt to use the UPS. Unplug the UPS and have it serviced 
immediately. 

UPS

 BEEPS OCCASIONALLY

 

Normal UPS operation when 
running on battery. 

None. The UPS is protecting the connected equipment. 

UPS

 DOES NOT PROVIDE EXPECTED BACKUP TIME

 

The UPS  battery module(s) are 
weak due to a recent outage or 
are near the end of service life. 

Charge the battery module(s). Modules require recharging after extended outages 
and wear faster when put into service often or when operated at elevated 
temperatures. If the battery module(s) are near the end of service life, consider 
replacing, even if the 

Replace Ba ttery

 LED is not illuminated.  

FRONT PANEL 

LED

S FLASH SEQUENTIALLY

 

The UPS has been shut down 
remotely through software or an 
optional accessory card.  

None. The UPS will restart automatically when utility power returns.  

ALL 

LED

S ARE OFF AND THE 

UPS

 IS CONNECTED TO UTI LITY POWER

 

The UPS is shut down and the 
battery is discharged from an 
extended outage. 

None. The UPS will return to normal operation when the power is restored and 
the ba ttery has a sufficient charge. 

BYPASS AND OVERLOAD 

LED

S ILLUMINATE

,

 

UPS

 EMITS A SUSTAINED ALARM TONE

 

The UPS is overloaded.  

The connected equipment exceeds the specified “maximum load” as defined in 

Specifications

 in the Quick Start Guide.  

The alarm remains on until the overload is removed. Disconnect nonessential 
equipment from the UPS to eliminate the overload condition.  

Summary of Contents for 1609-P10000E

Page 1: ...41063 261 01 1 990 2672 09 2005 Allen Bradley User Manual for 8000 10000 VA UPS 1609 P8000E 8000 VA 200 240 VAC 1609 P10000E 10000 VA 200240 VAC Tower Rack Mount 6U Uninterruptible Power Supply...

Page 2: ...rt Guide Removing the Batteries The unit is heavy To lighten the unit remove the batteries Refer to the unpacking instructions on the carton in which the unit is shipped Environmental Specifications T...

Page 3: ...6 Use appropriate glands to achieve strain relief on the hardwired input and output power cables Input Connection Output Connection optional Wire to L1 L2 Wire to L1A L2A System Wiring Voltage Current...

Page 4: ...3 Installing and Connecting the Batteries and Attaching the Front Bezel...

Page 5: ...up the UPS The battery charges to 90 capacity during the first three hours of normal operation Do not expect full battery run capability during this initial charge period OPTIONS q External Battery Pa...

Page 6: ...ely de energized from a remote location without switching to battery operation see EPO Option TVSS Screw The UPS features a transient voltage surge suppression TVSS screw for connecting the ground lea...

Page 7: ...ch Battery operation is not available while the UPS is in bypass mode see Troubleshooting Fault The UPS detects an internal fault see Troubleshooting Overload The connected loads are drawing more powe...

Page 8: ...ltage display Press and hold the button to view the utility voltage bar graph display After a few seconds the five LED Battery Charge display on the right of the front panel shows the utility input vo...

Page 9: ...nt Alarm Delay After Line Failure 5 second delay 5 second delay 30 second delay At Low Battery Never Mute ongoing alarms or disable all alarms permanently Shutdown Delay 20 seconds 0 20 60 120 240 480...

Page 10: ...bypass operation Output Voltage 208 230 V models 230 VAC 208 230 V models 200 208 220 230 240 VAC Allows the user to select the UPS output voltage while online Output Frequency Automatic 50 3 Hz or 6...

Page 11: ...uit UL CSA standards and an SELV circuit IEC standard Both Class 2 and SELV circuits must be isolated from all primary circuitry Do not connect any circuit to the EPO terminal block unless it can be c...

Page 12: ...nal battery packs Once the blank terminal window is open follow these steps to enter the number of battery packs Press ENTER to initiate terminal mode Press ENTER multiple times until the prompt User...

Page 13: ...outages Use caution when handling heavy battery modules Refer to Installing and Connecting the Batteries and Attaching the Front Bezel for battery replacement procedure reverse instructions for batte...

Page 14: ...or are near the end of service life Charge the battery module s Modules require recharging after extended outages and wear faster when put into service often or when operated at elevated temperatures...

Page 15: ...he battery connectors are fully engaged Weak battery Allow the battery to recharge for 24 hours Then perform a self test If the problem persists after recharging replace the battery Failure of a batte...

Page 16: ...Support Refer to Contact Information below 3 Pack the UPS in its original packaging Pack the UPS properly to avoid damage in transit Never use Styrofoam beads for packaging Damage sustained in transi...

Page 17: ...N Deenergizing Safety If the UPS has an internal energy source battery the output may be energized when the unit is not connected to a utility power outlet To deenergize a pluggable UPS press the OFF...

Reviews: