background image

 

14

 

P

ROBLEM AND 

P

OSSIBLE 

 

C

AUSE

 

S

OLUTION

 

BYPASS 

LED

 ILLUMINATES

 

The bypass switch has been 
turned on manually or through 
an accessory. 

If bypass is the chosen mode of operation, ignore the illuminated LED. 

If bypass is not the chosen mode of operation move the bypass switch on the 
back of the UPS, to the 

normal

 position. 

FAULT AND OVERLOAD 

LED

S ILLUMINATE

;

 

UPS

 EMITS A SUSTAINED ALARM TONE

 

The UP S has ceased sending 
power to connected equipment. 

The connected equipment exceeds the specified “maximum load” as defined in 

Specifications

 in the Quick Start Guide .  

Disconnect nonessential equipment from the UPS to eliminate the overload 
condition. 

Press the OFF button, then the ON button to restore power to connected 
equipment. 

FAULT 

LED

 ILLUMINATES

 

Internal UPS fault. 

Do not attempt to use the UPS. Turn the UPS off and have it serviced 
immediately. 

REPLACE BATTERY 

LED

 ILLUMINATES

 

Replace Battery

 LED flashes and 

a short beep is emitted every two 
seconds to indicate the battery is 
disconnected.  

Check that the battery connectors are fully engaged.  

Weak battery. 

Allow the battery to recharge for 24 hours. Then, perform a self-test. If the 
problem persists after recharging, replace the ba ttery. 

Failure of a battery self-test. 

The UPS emits short beeps for one minute and the 

Replace Battery

 LED 

illuminates. The UPS repeats the alarm every five hours. Perform the self-test 
procedure after the battery has  charged for 24 hours to confirm the 

Replace 

Battery

 condition. The alarm stops and the LED clears if the ba ttery passes the 

self-test. 

UPS

 OPERATES ON BATTERY ALTHOUGH LINE VOLTAGE EXISTS

 

Very high, low, or distorted line 
voltage. (Inexpensive fuel 
powered generators can distort 
the voltage.) 

Move the UPS to a different line circuit. Test the input voltage with the utility 
voltage display. 

DIAGNOSTIC UTILITY VOLTAGE

 

All five LEDs are illuminated.  

The line voltage is extremely high and should be checked  by an electrician. 

There is no LED illumination. 

If the UPS is plugged into a properly functioning utility power outlet, the line 
voltage is extremely low.  

ONLINE 

LED 

There is no LED illumination. 

The UPS is running on battery, or it is not turned on. 

The LED is blinking.  

The UPS is running an internal self-test. 

 

Summary of Contents for 1609-P10000E

Page 1: ...41063 261 01 1 990 2672 09 2005 Allen Bradley User Manual for 8000 10000 VA UPS 1609 P8000E 8000 VA 200 240 VAC 1609 P10000E 10000 VA 200240 VAC Tower Rack Mount 6U Uninterruptible Power Supply...

Page 2: ...rt Guide Removing the Batteries The unit is heavy To lighten the unit remove the batteries Refer to the unpacking instructions on the carton in which the unit is shipped Environmental Specifications T...

Page 3: ...6 Use appropriate glands to achieve strain relief on the hardwired input and output power cables Input Connection Output Connection optional Wire to L1 L2 Wire to L1A L2A System Wiring Voltage Current...

Page 4: ...3 Installing and Connecting the Batteries and Attaching the Front Bezel...

Page 5: ...up the UPS The battery charges to 90 capacity during the first three hours of normal operation Do not expect full battery run capability during this initial charge period OPTIONS q External Battery Pa...

Page 6: ...ely de energized from a remote location without switching to battery operation see EPO Option TVSS Screw The UPS features a transient voltage surge suppression TVSS screw for connecting the ground lea...

Page 7: ...ch Battery operation is not available while the UPS is in bypass mode see Troubleshooting Fault The UPS detects an internal fault see Troubleshooting Overload The connected loads are drawing more powe...

Page 8: ...ltage display Press and hold the button to view the utility voltage bar graph display After a few seconds the five LED Battery Charge display on the right of the front panel shows the utility input vo...

Page 9: ...nt Alarm Delay After Line Failure 5 second delay 5 second delay 30 second delay At Low Battery Never Mute ongoing alarms or disable all alarms permanently Shutdown Delay 20 seconds 0 20 60 120 240 480...

Page 10: ...bypass operation Output Voltage 208 230 V models 230 VAC 208 230 V models 200 208 220 230 240 VAC Allows the user to select the UPS output voltage while online Output Frequency Automatic 50 3 Hz or 6...

Page 11: ...uit UL CSA standards and an SELV circuit IEC standard Both Class 2 and SELV circuits must be isolated from all primary circuitry Do not connect any circuit to the EPO terminal block unless it can be c...

Page 12: ...nal battery packs Once the blank terminal window is open follow these steps to enter the number of battery packs Press ENTER to initiate terminal mode Press ENTER multiple times until the prompt User...

Page 13: ...outages Use caution when handling heavy battery modules Refer to Installing and Connecting the Batteries and Attaching the Front Bezel for battery replacement procedure reverse instructions for batte...

Page 14: ...or are near the end of service life Charge the battery module s Modules require recharging after extended outages and wear faster when put into service often or when operated at elevated temperatures...

Page 15: ...he battery connectors are fully engaged Weak battery Allow the battery to recharge for 24 hours Then perform a self test If the problem persists after recharging replace the battery Failure of a batte...

Page 16: ...Support Refer to Contact Information below 3 Pack the UPS in its original packaging Pack the UPS properly to avoid damage in transit Never use Styrofoam beads for packaging Damage sustained in transi...

Page 17: ...N Deenergizing Safety If the UPS has an internal energy source battery the output may be energized when the unit is not connected to a utility power outlet To deenergize a pluggable UPS press the OFF...

Reviews: